Actulux SVM EI 24V-8A Installationsanweisung - Seite 5

Blättern Sie online oder laden Sie pdf Installationsanweisung für Bedienfeld Actulux SVM EI 24V-8A herunter. Actulux SVM EI 24V-8A 13 Seiten. Control panel for fire ventilation

Actulux SVM EI 24V-8A Installationsanweisung
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Operation and connection of Manual Control Points
The Manual Control Point will generally contain the following:
Max. 8A
• Breakable glass window and red control button is activated by
pressure - this puts the control panel in ALARM condition, by
FUSE F1 - fast
which the motor output is activated (for normal service and testing
Actuator
the lid can be opened with a key).
Motor line monitor
• RESET button which brings the control panel out of the alarm
Ext 3 wire monitor (line 1)
J2
condition and starts the closing sequence for about 180 seconds.
Please note that RESET does not cancel errors on the system, e.g.
4
J3
line errors etc. These must be found and corrected.
3
• RED LED indicates that the control panel is in ALARM condition
2
and that the motor output either is or has been activated.
1
• YELLOW LED indicates faults on the system - please call for a
Max. Torque 0.5 Nm
1
2
3
service technician.
N 1
Line 1
• GREEN LED indicates that the system is in normal operation
Actuator
24V Out
condition without errors.
CONNECTION of the fire switch is made as shown on the drawing.
The installation with fire switches must be terminated with a 10 KΩ or
27 KΩ resistor in the last switch in order to establish the line monitoring
correctly – this can either be done by moving the factory mounted resistor
from the terminal strip to the last fire switch or connect jumper J1 in
the fire switch type BVT is mounted (by this a 10 KΩ resistor is also
2
1
connected).
Blue
Blue
By means of DIP switches the control panel has different possibilities of
5
7
settings for the input to the fire switch:
M1
DIP 1 (Conf. firesw.):
M2
On = ALARM condition from 500-3 KΩ, (indication of line error by direct
6
8
short circuit or open circuit).
Brown
Brown
Off = ALARM condition from 0-3 KΩ (indication of line error by open
3
4
circuit).
2 channel LIP 6
DIP 2 (Failsafe):
Next LIP
On = Any line error on fire switch or smoke detector puts the control panel
in ALARM condition. This function can be used if cables to fire switches
and smoke detectors are not fireproof.
Off = An error condition does not report ALARM condition.
BVT
1 green LED OK (lights when OK and while closing)
2 yellow LED (lights on error)
3 red LED alarm (emergency opening)
4 ground (-)
5 not used
6 fire switch reset
7 fire switch emergency opening
Jumper J1 must only be set in the last or only fire switch
BLUE
DOME OPEN
ON
OFF
DIP NO
PE
L1
N 1
10
11 12
4
5
6
7
8
9
10
11
12
Alarm Out
Failure Out
Manuel Control Point
1 Cannel LIP 7
1
2
Blue
5
M1
1
2
3
6
Brown
2
1
10 KΩ
Fire switch BVT No. 1
3
1
2
Next LIP
1
2 3
2,2Ω
2 3
10 KΩ
1
Fire switch BVT No. 1
1
2
3
10 KΩ
2
3
1
Fire switch type BVT.
2,2Ω
Fit J1 in last BVT for
10 KΩ
line monitoring
Extra relay print #111933
Fire switch type BVT
Fit J1 in last
provides 2 additional
BVT for line monitoring
potential free contacts
each 30V 0,5A
24V
1
LED
OK
Grøn/Green
Grün/Vert
24V
2
LED
Gul/Yellow
Gelb/Jaune
3
Buzzer
LED
Buzzer
Alarm
24V
4
Rød/Red
GND
Rot/Rouge
6
Reset
Reset
2,2 KΩ
7
Alarm
10 KΩ
Jumper
J1
8
Max. 8A
DIP settings see page 13
FUSE F1 - fast
END termination
J7
Actuator

Auto reset

Motor line monitor
BUS Slave
J6
When setting OPTION(DIP8) On, an automatic reset is performed 2 seconds after the fire signal is
Ext 3 wire monitor (line 1)
J2
removed. (From software version V1.005)
START termination
J4
4
J3

Connection of smoke-/heat detectors

BUS Master
J5
3
Smoke- and heat detectors are connected as shown.
2
1
Line monitoring: Correct line monitoring can only be guaranteed with detectors
1
2
Max. Torque 0.5 Nm
delivered from the supplier. Other detectors may have different internal resistances
Max. Torque 0.5 Nm
1
2
3
and stand by power consumption.
Line 1
Actuator
Comfort ventilation – Connection and settings
24V Out
The motor output can be controlled separately with a comfort switch.
13
14
15
For comfort ventilation there are the following possibilities:
13
16
17
18
19
20
14
15
Smoke
Comfort
Potentiometer in Puls pos.:
It is possible to press the »up« button 3 times, which each gives 6 seconds of opening
time - after that nothing happens – Continuous »up« signal gives 3x6 sec.=18 sec.
- One press on »down« closes the actuator completely for a period which is 18 sec.
longer than the complete opening time - In order to avoid »actuator pumping« max. 3
successive closing attempts will be allowed.
2
1
Potentiometer in Const. pos.:
As long as »up« signal or »down« signal are given, the actuators are running
Blue
Blue
4
6
7
Potentiometer in Puls variable pos.:
5
7
L1 In
2,2KΩ
The time on the above mentioned pulse opening can be adjusted from 0-60 sec. on the
L2
M1
J1
potentiometre.
M2
No.1
Down
L1 O ut
4
6
7
When moving the potentiometer into the different positions the LED batt low will
6
8
4
6
7
Brown
flash for about 4 sec. to indicate when in puls mode. LED line fail flashes 4 sec. when
Brown
4
6
Up
J1
7
in constant and AC fail flashes when in puls varaiable.
3
4
L1 In
2 channel LIP 6
2,2KΩ
6
4
7
L2
J1
4
7
6
Nr.2-20
Next LIP
L1 O ut
J1
(only last sensor)
Actulux A/S
Haandvaerkervej 2
Room thermostats, weekly timers, CCS and
DK 9560 Hadsund
other external control equipment for comfort
Denmark
ventilation can be connected on the input of the
comfort control.
DRAWN BY: PSP
TITLE:
ENGELSK
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
®
®
®
®
Connection from
prev. unit.
4
5
6
7
8
9
10
Alarm Out
Failure Out
21
22
23
24
25
26
27
Weather
Prior
1
1
1
AWR-24
24V
AC/DC
Extra relay print #111933
Potmeter for
comfort feature
provides 2 additional
Max.
potential free contacts
YEL
YEL
YEL
each 30V 0,5A
AC FAIL
LINE FAIL
BATT LOW
Min
18
19
Phone int.: +45 98 57 40 90
Fax int.:
+45 96 15 28 00
www.actulux.com
DATE: 26-09-17
SIZE:
A4
DWG NO.:
Down
211704_03
Up
9
START termi
Max. Torque 0.5 Nm
11
12
13
14
15
16
17
18
Manuel Control Point
Smoke
Comfort
#111980
Firemans Priority switch
CLOSE
OPEN
R
E
S
E
T
1
6
2
3
4
6
7
L1 In
2,2KΩ
L2
10 KΩ
J1
No.1
Fire switch BVT No. 1
L1 O ut
2 3
4
6
7
2 3
4
6
7
L1 In
2,2KΩ
10 KΩ
L2
J1
Nr.2-20
Fire switch type BVT.
L1 O ut
Fit J1 in last BVT for
line monitoring
(only last sensor)
#111960
#111961
20
SHEET:
SCALE:
2 OF 4
1:1
REV:
BUS M
19
2
Down
Up
C
D