The strings the pager sends always begin with '#' and end with '\r' (0D hex).
Evacuation:
Alarm on loop 1:
Alarm on loop 2:
Alarm on loop ..:
Alarm on loop 10:
Mains fault:
Battery fault:
Fault:
Reset:
Test position on:
Out of use:
T1 starting:
T1 stopping:
T3 starting:
T3 stopping:

11 Operating panel

The operating panel can be used for the complete operation of the control panel. Simple settings
such as delay times can be entered from the operating panel. The CMPlus.exe program is used
for more advanced settings.
The labels in the label pockets can be changed, for example for indications in another language.
See the end of this manual for labels in other languages.
#FAL,EVA
#FAL,L01
#FAL,L02
#FAL,L..
#FAL,L10
#FLT,MNS (a mains fault also sends #FLT)
#FLT,BAT
(a battery fault also sends #FLT)
#FLT
#RES
#TPO (also after rest if at least 1 loop is in the test position)
#OOU (also after reset if at least 1 loop is out of use)
#T1A
#T1E
#T3A
#T3E