GENERAL INFORMATION
1.1
SYSTEM DESCRIPTION
Digitize to Monaco
D-7000 interface
This document will familiarize you with the operation of the Digitize SYSTEM 3500 for
processing Monaco BT-2 Alarms/Troubles/Restores.
There are two modes of operation for the Bangor/Keyport and Whidbey systems.
Normally the system will be set up to process the Monaco BT Alarms and pass them to
the RDC. In this operation, the SYSTEM 3505 will be ASLEEP but can always be
Awakened by simply pressing the CLEAR key. The CLEAR key should be blinking its
red LED. When awake, the SYSTEM 3505 will auto Acknowledge its alarms as long as
it is communicating with RDC. The SYSTEM can be left awake or asleep while it is
passing its alarms to the RDC.
Should the data connection between the SYSTEM 3505 and the RDC fail, the SYSTEM
3505 will automatically wake up within approximately 30 seconds, and annunciate the
fault condition and any additional new Alarm, Trouble or Restore conditions. If left
alone, the alarms will process as soon as the data link is restored. If the SYSTEM 3505
was asleep prior to the link fault, it will go back to sleep when the link restores, providing
you did not press the CLEAR key.
The second mode of operation is to have the operator, located in the same room as the
SYSTEM 3505 Acknowledge the Alarms. The Alarms will still be passed through to the
RDC, but the Alarms will continue to annunciate at the local SYSTEM 3505 until such
time that the ACKNOWLEDGE key is pressed. DO NOT PUT THE SYSTEM 3505
INTO THE SLEEP MODE IF YOU ARE MONITORING THE ALARMS LOCALY. If
this mode is going to be used for long periods of time, the SLEEP key can be disabled by
the service personnel. Do not leave the unit unattended if you elect to acknowledge the
alarms locally at the SYSTEM 3505. An Unacknowledged Alarm will not report its
restoral condition until such time as the Alarm, or Trouble condition is Acknowledged.
DIGITIZE, INC. 700270 REV A 01/06
1-1
Specifications Subject to Change Without Notice