2-0 Mounting Instructions
Each module can be mounted on a DIN rail for fast installation and easier
maintenance. Each module also has two pre-molded mounting holes all-
owing the module to be mounted in a panel or on a wall.
2-1 Mounting Positions
The controller's mounting orientation must be horizontal with the
controller's back attached to a vertical wall surface (Figure 06).
Figure 06: Permitted Mounting Positions - Vertical Mounting is Forbidden
Horizontal Mounting Position:
Required for DIN rail mounting
Required for wall mounting
2-2 Assembly Order
Modules are connected in a left to right order, starting with a PS24 Power
Supply then the ECLYPSE A1000 server module and then the 8UI6UO
module.
2-3 DIN Rail-Mounted Installation
1.
Securely mount the DIN rail horizontally on the wall.
2.
Clip the modules onto the DIN rail in the assembly order.
3.
Slide the modules together so that the side connectors of each
module arefirmly mated with the adjoining module. Use DIN rail
clips to keep the row of modules well secured together and to
prevent the movement of any module along the DIN rail. Certain
modules come with DIN rail clips in the box.
4.
To detach the module from the DIN rail, separate the module
from any other module located on either side. Use a flat screw
driver to pull down on the release clip located at the bottom
center of the module and pull it off the DIN rail, bottom first.
Figure 07: DIN Rail Release Clip
2-4 Wall Mounted Installation
Modules should be mounted on a wall one module at a time. The first
module of the assembly to be mounted should be the one to the very left
(usually a PS24 Power Supply). Once this module has been attached to the
wall, connect the next module on the right so that the side connectors are
firmly coupled and the modules are aligned straight. Now attach this
module to the wall. Repeat until all modules are mounted in a row.
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitybrands.com © 2019 Acuity Brands Lighting, Inc. All rights reserved. Rev. 11/07/2019
Vertical Mounting Position:
Is Forbidden
2-4 Wall Mounted Installation - cont'd
1.
Before mounting a module, separate the front assembly from the
back plate of each module to be mounted: push the two latches
up to unlock a module's front assembly as shown below
•
For server and power supply: Separate the front and back base
by gently pulling the front assembly off of the back base, thereby
separating the electrical connectors between the two halves.
Figure 08: Latches to Unlock a Module's Front Assembly
2.
Once the front assembly has been removed, use the back plate's
mounting holes to mark the location of any holes that need to be
drilled.
Figure 09: Typical Mounting Holes
3.
Drill the holes.
4.
Clean the surface and mount the module using a No. 8 slotted
hex, size: 1/4" or equivalent mounting hardware appropriate to
the wall.
Figure 10: Appropriate Mounting Hardware (field supplied)
5.
To lock a module's front assembly in place, attach the front
assembly to the module's back base by closing any gull-wing
front assemblies (if applicable) and pushing the two latches
down.
5 of 14