Arico V300 Benutzerhandbuch - Seite 3
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Temperaturregler Arico V300 herunter. Arico V300 4 Seiten. V series
(31)Dimension
(32)Alarm Function
Alarm Range :
It's avalible to set alarm
range from
0 to 99 in unit
or
Alarm Hysteresis band :
It's avalible to set alarm
hysteresis band from 0 to 10
in unit
or
And avoid temperature to
unstable and fast change in
critical point.
Alarm range
Alarm range
(41)Other Parameter Function
1. Password
Password has 4 digits.The units digit controls the using of
parameter level 1~4, the tens digit controls the setting of
Parameter level 1~4, and the other digits should be set by 0.
The example is the following :
Password = 0023
The parameter level 1~3 can be used and the level 1~2 can
be set.
2. Thermocouple type
J0 TYPE
J TYPE without DP,Range: 0~900 °C / 32 1200
J1 TYPE
J TYPE with DP, Range: 0.0~900.0 °C / 32.0~999.9 °F
K0 TYPE
K TYPE without DP,Range: 0~1200 °C / 32~1500 °F
K1 TYPE
K TYPE with DP, Range: 0.0~999.9 °C / 32.0~999.9 °F
PT0 TYPE
PT TYPE without DP,Range: -200~500 °C / -328~900 °F
PT1 TYPE
PT TYPE with DP, Range: -199.9~500.0 °C / -199.9~900.0 °F
*DP:Decimal point
3. Unit
The unit :
or
4. Temperature Offset
The tem
-99~+99
/
perature offest range :
5. M ain Output Percentage High Lim it :
This function can magnify and minify
the output percentage
of PID control.
The related equation as the following:
Output percentage after tuning = ( output percentage before
tuning * output percentage high lim
6. Aux. Output Percentage High Lim it :
This function can magnify and minify the output percentage
of PID control. The related equation as the following:
Output percentage after tuning = ( output percentage before
tuning * output percentage high limit ) / 100
7. Restore The Default :
This function will restore the default from the user's settings.
No alarm
Low limit
High limit
Lo/Hi limit
Low limit standby
Lo/Hi limit standby
Reverse Lo limit
Reverse Hi limit
Reverse Lo/Hi limit
Absolute
Reverse Absolute
Alarm range
Alarm range
~
°F
TC type
PT type
JP1
Open
Short
JP2
Short
Open
it ) / 100
Unit: mm
Model
(33)ON/OFF Control
In ON/OFF control type, we can
set ON/OFF hysteresis band to
control temperature in desired range.
(34)Manual Control Type
The user can force to set output percentage.
(35)Output Function
1. Relay Output :
It's better to set output cycle time >20sec in relay output. The setting
time is larger and the duration of relay is longer.
2. Digital voltage Output :
It's available to set output cycle time from 1 to 60 sec as user's
need in digital voltage output (24V).
3. Analog Output :
It's available to set the high and low limits of analog output after
the value of output cycle time equal 0. The range of analog
output are 0~20mA or 0~10V.
(42)Error Messages
Thermocouple
breaking
(43)Special Function
1.PID Self Tuning :
The condition for starting : Present value should be lower than
setting for 45
. Present value will flash during executing
self-tuning.
2.Manual Output Control :
Under manual output control,setting value is manual output
percentage and setting output key to tuning output percentage
directly.
(44)Order Code
1
2
1:
Mode
V100:48 × 48 mm
V200:48 × 96 mm
V300:72 × 72 mm
V400:96 × 96 mm
V500:96 × 48 mm
2 3:Main Output / Aux. Output
/
O:None
R:Relay ( * )
V:Digital volt. Output 24V/20mA
I:Analog current output 0~20mA, 4~20mA
L:Analog volt. output 0~10V, 0~5V, 1~5V
ON/OFF hysteresis band
3
4
5
4 / 5:Alarm 1 / 2
O
None
:
R
Relay ( * )
:
V
Digital volt. output 24V/20mA
: