NOTE:
Wiring of the wall switch must be completed prior to installing the unit.
NOTE:
Use a double pole, single throw wall switch that is rated for 20 amps.
NOTE:
Only install a wall switch on units that do not have a remote control.
240 VOLT INSTALLATIONS
The wall mounted switch is connected to the fireplace by running a 2 conductor wire with a ground from the junction
box on the back of the unit to the thermostat.
1. Locate the switch on the top corner of the unit.
2. Ensure that the switch is in the 230 volt position.
3. Loosen the screw securing the junction box cover and remove the cover.
4. Remove the knockouts (if necessary) or use the provided cable clamp.
5. Pull out the four wires marked L1, L2, N, and G.
6. Connect one of the wires from the wall switch to the black L1 wire on the unit, and the other wire from the
wall switch to the L1 from the power supply.
7. Connect one of the wires from the wall switch to the red L2 wire on the unit, and the other wire from the
wall switch to the L2 from the power supply.
8. Connect the ground wire from the wall switch to the ground wire from the power supply.
9. Connect the white N wire from the unit to the neutral from the power supply.
10. Connect the green ground wire from the unit to the ground from the power supply.
11. Ensure that all connections are tight. Insert all the wiring into the unit and secure with a cable clamp.
MAIN POWER WALL SWITCH WIRING