Function description
Signal that is longer than10s does not cause a reset.
For parameterization of the acknowledgment function see chapter " Configuration of the switching
threshold and acknowledgement".

Functional diagram

Automatic acknowledgement V-LIMIT 1 and V-LIMIT 2
(V-LIMIT 1 must be at least 1.1Hz!)
f
V-LIMIT2
Hysteresis
Hysteresis
V-LIMIT1
1 Hz
0,5 Hz
t
A
13/14, 23/24
Q-autom.
1
2
3
1
Start-up monitoring time starts if f>1Hz
2
Start-up monitoring time is expired. Enabling
current path remains closed because f>V-LIMIT
1.
3
Enabling current path opens because f<V-LIMIT
1.
4
Enabling current path closes, if f<0,5Hz.
5
Start-up monitoring time starts if f>1Hz.
6
Start-up monitoring time is expired. Enabling
current path opens because f < V-LIMIT 1.
7
The setpoint speed was reached outside of the
minimum switch-off time. Enabling current path
closes.
8
The setpoint speed was reached within the min-
imum switch-off time. Enabling current path
closes after 0.5s.
18-09-27 / 33pd02-V0743
>t
t
min
A
4
5
6
7
Manual acknowledgment V-LIMIT 1 and V-LIMIT 2
f
V-LIMIT2
Hysteresis
Hysteresis
V-LIMIT1
<t
t
min
A
13/14, 23/24
Q-manuell
1
2
8
1
Start-up monitoring time starts with the falling
edge of the acknowledgement signal.
2
Start-up monitoring time is expired. Enabling
current path remains closed because f>V-LIMIT
1.
3
Enabling current path opens because f<V-LIMIT
1.
4
Start-up monitoring time starts with the falling
edge of the acknowledgement signal.
5
Start-up monitoring time is expired. Enabling
current path opens because f < V-LIMIT 1.
6
Start-up monitoring time starts again.
7
Start-up monitoring time is expired. Enabling
current path remains closed.
8
Enabling current path closes because
V-LIMIT 1<f<V-LIMIT 2.
t
t
A
A
3
4
5
6
7
8
9