Ariston GENUS PREMIUM EVO HP 65 Konstruktions-, Installations- und Wartungsanweisungen - Seite 33

Blättern Sie online oder laden Sie pdf Konstruktions-, Installations- und Wartungsanweisungen für Boiler Ariston GENUS PREMIUM EVO HP 65 herunter. Ariston GENUS PREMIUM EVO HP 65 44 Seiten. Wall-hung condensing gas boiler hp
Auch für Ariston GENUS PREMIUM EVO HP 65: Benutzerhandbuch (17 seiten), Benutzerhandbuch (24 seiten), Benutzerhandbuch (32 seiten)

Ariston GENUS PREMIUM EVO HP 65 Konstruktions-, Installations- und Wartungsanweisungen
description
notes
SERVICE CODE
Rotate encoder clockwise to select code 234 and press O
COMPLETE MENU
0 NETWORK
0. 2 BUS NETWORK
0. 2. 0 Network Presence
Indication of the devices connected via BUS.
0. 4 BOILER USER INTERFACE
0. 4. 0 Zone to be set by display
0. 4. 2 Thermoregulation button
deactivation
2 BOILER PARAMETERS
2. 0 GENERAL
2. 0. 0 DHW Setpoint
Temperature
Setting by DHW button 2
2. 2 BOILER GENERAL SETTINGS
2. 2. 0 Soft ignition
2.2.0 Soft ignition
Maximum value
Minimum value
see Table summarising changes
2. 2. 3 Underfl oor thermostat
or zone 2 ambient
thermostat selection
2. 2. 4 Termoregulation
Termoregulation can be activated by pressing the AUTO
button.
2. 2. 5 Heating ignition delay
2. 2. 8 Boiler version
ATTENTION !
Modify from 1 to 2 only
with connection to an
external storage with
thermostat ON/OFF
ONLY FOR SERVICE - To be used only in substitution P.C.B.
2. 2. 9 Set boiler heat power
ONLY FOR SERVICE - To be used only in substitution P.C.B.
value
K
Boiler
from 1 to 3 (nr)
0 = Enabled AUTO
button
1= Disabled AUTO
button
from 40 to 60 (°C)
from 0 to 100
60 %
100%
0%
0 = Floor safety
thermostat
1 = Zone 2 ambient
thermostat
0 = Absent
1 = Present
0 = Deactivated
1 = 10 seconds
2 = 90 seconds
3 = 210 seconds
from 0 to 5
0 = NOT USED
1 = storage with
NTC
2 = storage with
thermostat
3 = NOT USED
4 = NOT USED
5 = NOT USED
description
notes
2. 3 CENTRAL HEATING PARAMETER - PART 1
2. 3. 1 Maximum Central Heating
power Adjustable heating
see Table summarising changes
2. 3. 2 D.H.W. Maximum power
percentage
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 3 Minimum power
1
percentage
0
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 4 C. Heating Maximum
power percentage
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is
changed - see Table summarising changes
2. 3. 5 Anti-cycling time mode
2. 3. 6 Anti-cycling time
(If 235 = 0)
2. 3. 7 Central Heating pump
overrun
2. 3. 8 Pump speed control
GENUS PREMIUM EVO HP 45/65/85*/100*
*= with Optional Pump Kit (Two speed)
2. 3. 9 Set Delta T Pump
Parameter to set if Pump Speed control (237) is setted
on modulating
GENUS PREMIUM EVO HP 45/65/85*/100*
0
*= with Optional Pump Kit (Two speed)
ΔT (fl ow - return) for circulation pump modulation
This parameter can be used to set the diff erence
between the fl ow and return temperatures, which
0
determines the commutation between low and
high circulation pump speed. E.g.: param. 14 = 20
if the Tfl ow - Tret > 20°C; the circulation pump will
be activated at maximum speed. If the Tfl ow - Tret
0
< 20 - 2°C; the circulation pump will be activated at
minimum speed.
The minimum wait time between speed changes is 5
minutes.
1
2. 4 CENTRAL HEATING PARAMETER - PART 1
2. 4. 1 Central heating circuit
pressure to signal a fi lling
request
if the pressure falls down to the pre-set alert value, the
boiler will signal a malfunction warning (1P4
insuffi cient circulation; the request for re-establishing the
correct value will appear on the display.
2. 4. 3 Post-ventilation after
Central Heating request
technical area
value
from 0 to 100
from 0 to 100 (%)
from 0 to 100 (%)
from 0 to 100 (%)
0 = Manual
1 = Automatic
from 0 to 7
(minutes)
from 0 to 15 (minutes)
o CO (continuos)
0 = Low speed
1 = High speed
2 = Modulating
from 10 to 30 (°C)
from 4 to 8
(0,x bar)
Warning 1P4
Filling Needed
ALERT
0 = OFF
1 = ON
60
100
100
1
3
3
2
20
6
1P4) for
0
33