ABB ACS 800 Series Handbuch - Seite 10

Blättern Sie online oder laden Sie pdf Handbuch für Kontrolleinheit ABB ACS 800 Series herunter. ABB ACS 800 Series 16 Seiten. Converter modules with electrolytic dc capacitors in the dc link
Auch für ABB ACS 800 Series: Benutzerhandbuch (14 seiten), Hinweis zum Einbau (2 seiten)

ABB ACS 800 Series Handbuch
10 Reforming the capacitors
If the non-operational time has been more than two (graph a) or three (graph b) years,
reform the converter using the method in section
supply
on page
11
or
Reforming time (hours)
6
5
4
3
2
1
1/2
0
0
a) Product series ACS800, ACS850, ACQ810, ACSM1, ACS880-104, ACS380, ACH480 and
ACS480
b) Product series ACH580, ACQ580, ACS580 and ACS880 except ACS880-104

Checking the converter age

The converter serial number defines the week when the converter was manufactured:
7 digits: For example, in 3260034, 3 denotes manufacturing year (2003), 26
manufacturing week and 0034 running manufacturing number.
8 digits: For example, in 14250125, 1 denotes manufacturing country (1 = Finland), 4
manufacturing year (2004), 25 manufacturing week and 0125 running manufacturing
number.
10 digits: For example, in 1173200725, 1 denotes manufacturing country, 17
manufacturing year (2017), 32 manufacturing week and 00725 running manufacturing
number.
Reforming with external diode bridge
a
1
2
Reforming with external DC power
on page 13.
b
3
4
Non-operational time (years)
5
6