Troubleshooting
10
Problem
"Normal" Output/Primary
Discharge not operating
"Discharge Delay"
Output/Secondary Discharge
not operating
Fault displayed on fire control
panel (3 Beeps)
For additional assistance contact your supplier.
Specifications
11
Dimensions
Enclosure material
Operating voltage
Outputs
Outputs Fuse
Discharge end-of- line
Fault-sensing
Operating Temp.
Ingress Protection
Max no. of Modules
Possible Cause
Disconnected or poor
connection to FirePro generators
Incorrect programming at fire
control panel
OR
Disconnected or poor
connection to FirePro generators
Disconnected or poor
connection to FirePro generators
OR
Number of installed generators
exceeds maximum
OR
FirePro Generators have
discharged
FP-08850
140L x 65W x 30D
Die Cast Aluminium
12-30VDC
Discharge, max 2A at 12VDC and 2A at 24VDC
Self-resetting Polyswitch trips at 2A
3K3 resistor
Discharge wiring open-circuit
40 to 85 degrees Celsius
IP65
Up to 10 – If more modules are required, consult with your
supplier.
Actual maximum will be determined by delay programming.
Solution
Check connection of any
extension cables.
Check programming at fire
control panel.
Check connection of any
extension cables.
Check connection of any
extension cables.
Inspect condition of FirePro
Generators.
Check internal battery of FirePro
Test lamp.