Whirlpool WVU17UC0JW Installationsanleitung und Gebrauchs- und Pflegeanleitung - Seite 6
Blättern Sie online oder laden Sie pdf Installationsanleitung und Gebrauchs- und Pflegeanleitung für Lüftungshaube Whirlpool WVU17UC0JW herunter. Whirlpool WVU17UC0JW 24 Seiten. 30" 76.2 cm
Auch für Whirlpool WVU17UC0JW: Installationsanleitung und Gebrauchs- und Pflegeanleitung (24 seiten)
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
Vent System
Vent Piece
45° elbow
2.5 ft (0.8 m)
90° elbow
5 ft (1.5 m)
7" (17.8 cm) wall
0 ft (0 m)
cap
Example vent system
90˚ elbow
2 ft (0.6 m)
1 - 90° elbow
1 - wall cap
8 ft (2.4 m) straight
System length
Maximum Recommended Length
7" (17.8 cm) Round Vent
6
Wall cap
6 ft (1.8 m)
= 5 ft (1.5 m)
= 0 ft (0 m)
= 8 ft (2.4 m)
= 13 ft (3.9 m)
= 50 ft (15.2 m)
Electrical Requirements
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance with National Electrical Code, ANSI/NFPA 70
(latest edition), or CSA Standards C22.1-94, Canadian Electrical
Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local
codes and ordinances.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 V, 60 Hz, AC only, 15 A, fused electrical circuit is
■
required.
If the house has aluminum wiring, follow the procedure
■
below:
Connect the aluminum wiring using special connectors
and/or tools designed and UL listed for joining copper to
aluminum.
Follow the electrical connector manufacturer's recommended
procedure. Aluminum/copper connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections must conform with the rating of
■
the appliance as specified on the model/serial rating plate.
The model/serial plate is located behind the filter on the rear
wall of the range hood.
Wire sizes must conform to the requirements of the National
■
Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22. 1-94, Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.