4.1.16 Pump speed control
nMN:
Pump speed control
Adjustment range: 30 ... 100
Factory setting: 40
4.1.17 Operating mode
HND1 / HND2:
Operating mode
Adjustment range:
OFF, AUTO, ON
Factory setting: AUTO
4.1.18 Language
LANG:
Language choice
Adjustment range:
dE, En, It, Fr
Factory setting: En
4.1.19 Unit
UNIT:
Adjustment of unit
Adjustment range: FAH, °C
Factory setting: FAH
| 16
A relative minimum pump speed is allocated to the output
R1 via the adjustment channel nMN.
Attention:
When loads which are not speed controlled (e.g.
valves) are used, the value must be changed to 100 %
in order to deactivate pump speed control.
For control and service work, the operating mode of the
controller can be manually adjusted. For this purpose, select
the adjustment value HND1 / HND2. The following adjust-
ments can be carried out:
• HND1 / HND2
Operating mode
OFF
:
relay off
AUTO :
relay in automatic operation
ON
:
relay on
In this channel, different languages are available.
• dE : German
• En : English
• It : Italiano
• Fr : French
The menu unit can be adjusted:
• °FAH
• °CEL
(flashing) +
(flashing) +