1 Zone Alarm - Model VA01A
Operation, Maintenance and Installation Manual
Installation of the Versa'larm
1. To install/replace the battery for the backup power feature, remove the access cover (Fig. 1) and install 9 VDC
battery (Duracell model MX 1604B2) (Fig. 2). After installing battery, press the test button (Fig. 3) to activate the
alarm to make sure the battery works properly. The alarm indicator light should illuminate and the buzzer should
annunciate. If using the auxiliary contacts, leave cover off until Step 4 is completed. If you are not using the
auxiliary contacts, replace the access cover (Fig. 4).
Remove Cover To Insert 9v
Battery. Replace Yearly.
Auxiliary Contacts Inside.
(Fig. 1)
2. Determine mounting location for the Versa'larm. Make sure the power outlet is within 5 feet of the Versa'larm
(Fig. 5). Make sure the outlet is on a separate circuit breaker from any other device and not on a switched
receptacle to maintain power integrity. Mount the Versa'larm using two #6 self tapping screws (not included)
(Fig. 6). Use #8 plastic anchor (not included) if mounting to sheet rock (Fig. 7).
5 ft max
(Fig. 5)
3. If you are not using the auxiliary contacts, go to Step 6. If using auxiliary contacts (Fig. 8), when a sensor such
as a float switch in a septic tank, a WaterSpotter™ near a floor drain or in your sump pit is activated, it will close
relay contacts on Terminals 1A and 1B and activate the Auto Dialer. If connecting to existing alarm security
system or BAS system, go to Figure 9 on Page 3. When connected, replace the access cover and pull the wires
through the knockouts on the access cover (Fig. 10 and Fig. 11), see Step 5.
route all wires away from sharp objects and internal components.
Terminals 1 and 2
Auto Dialer Power Supply
RED = "+"
BLACK = "-"
Terminals 3 and 4
Auto Dialer Contacts
YELLOW = 1A
WHITE = 1B
Alarm Systems
Control Panels
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
TM
Remove Cover To Insert 9v
Battery. Replace Yearly.
Auxiliary Contacts Inside.
(Fig. 2)
To Phone Line
Float Switches
Leak Detection Systems
(Fig. 3)
(Fig. 6)
Caution!
- When installing wires,
(Fig. 8)
+ -
1A 1B
P/N: 101444
Remove Cover To Insert 9v
Battery. Replace Yearly.
Auxiliary Contacts Inside.
(Fig. 4)
(Fig. 7)
+
-
1A 1B
Page 2 of 4