Vizzyalarm™ 3-Zone WiFi Alarm Panel - Installation Instructions
Installation of the Alarm Panel
3. If connecting to an existing alarm security system or building automation system (BAS), use 18 gauge 2-conductor wire
to connect the existing product to the auxiliary contact inputs on the terminal block (Fig. 7). See below for wiring
information. The zone-1, zone-2, and/or zone-3 auxiliary contacts are activated when the sensor (signaling device)
contacts are "closed" during an alarm condition (normally open or normally closed). When connected, run the wire(s)
towards the bottom/center of the alarm panel to go through the wiring access hole once the enclosure cover is replaced
(Fig. 9 and Fig. 10).
4. Connect the sensor (signaling device) to the sensor/signaling device inputs on the terminal block (Fig. 8). See
below for wiring information. The zone-1, zone-2, and/or zone-3 alarms are activated when any "dry" type sensor
that "closes" during an alarm condition (normally open or normally closed). When connected, run the wire(s) towards
the bottom/center of the alarm panel to go through the wiring access hole once the enclosure cover is replaced
(Fig. 9 and Fig. 10).
Note: When installing a sensor or device, always refer to its installation instructions for complete operating information.
CAUTION: Route all wires away from sharp objects and internal components when installing wires.
Auxiliary Contacts:
Zone-1 (1A)
One wire to Terminal COM (common)
One wire to Terminal 1A
Zone-2 (2A)
One wire to Terminal COM (common)
One wire to Terminal 2A
Zone-3 (3A)
One wire to Terminal COM (common)
One wire to Terminal 3A
30VDC, 700mA maximum, Normally Open; Single Pole, Single Throw
Note: The auxiliary dry contacts of the alarm panel are normally open ONLY,
recommended to use 18 gauge 2-conductor wire. Used for remote monitoring.
Sensor/Signaling Device:
Zone-1 (CH1)
One wire to Terminal COM (common)
One wire to Terminal CH1
Zone-2 (CH2)
One wire to Terminal COM (common)
One wire to Terminal CH2
Zone-3 (CH3)
One wire to Terminal COM (common)
One wire to Terminal CH3
3-10VAC/DC, 10mA minimum, Normally Open or Normally Closed
Note: Use normally open sensors (signaling device) for high level alarm indication
and normally closed sensors (signaling device) for low level alarm indication.
5. After the wiring is completed and before replacing the enclosure cover, run the wire(s) towards the bottom/center of the
alarm panel to go through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).
CAUTION: Route all wires away from sharp objects and internal components when installing wires.