Alderon Industries Wireless Versa'larm VA01B Handbuch für Betrieb, Wartung und Installation - Seite 2
Blättern Sie online oder laden Sie pdf Handbuch für Betrieb, Wartung und Installation für Sicherheitssystem Alderon Industries Wireless Versa'larm VA01B herunter. Alderon Industries Wireless Versa'larm VA01B 6 Seiten. 1-zone alarm
Wireless Versa'larm
1-Zone Alarm - Model VA01B
Part Numbers - 7991 and 7992
Operation, Maintenance and Installation Manual
Alarm System Product Overview
1
Electrical Ratings
• Single Phase
• 120VAC/9-11.1 VDC
• 50/60 Hz
Pretest the Alarm System and Testing Alarm Panel
1. The wireless transmitter and receiver are both programmed in the factory and do not need to be adjusted or
programmed. Important! - Allow 10 minutes after the Versa'larm™ is powered up to establish a communication link with
the float switch and wireless transmitter. Wait at least 10 minutes before attempting to test the system.
NOTE: THE WIRELESS TRANSMITTER CAN BE ACTIVATED BY OPENING THE COVER AND PRESSING THE
BLACK BUTTON FOR FIVE SECONDS.
a. Pretest the system before mounting wireless transmitter, float switch, wireless receiver, and alarm panel.
b. Plug the alarm panel into a power outlet (120 VAC, 50/60 Hz).
c. Attach the float switch (black) to the wireless transmitter (yellow) using the screw in quick connect/disconnect.
d. Tilt the float switch above horizontal to activate the alarm panel (keep above horizontal through step 3). Press and
hold the "Alarm Test" pushbutton to test system weekly after installation or when testing the battery backup feature.
2. Once the float switch activates the alarm panel, the buzzer should annunciate and alarm LED (red) should illuminate.
3. Press the "Alarm Silence" pushbutton, the buzzer should silence while the alarm LED (red) remains on.
4. Tilt the float switch below horizontal to deactivate the alarm panel, the alarm LED (red) should turn off. If performing the
weekly test or testing battery backup, release pressure from the "Alarm Test" pushbutton.
5. The "Auto Reset" function will reset the system after alarm condition is cleared for the next alarm cycle.
6. Repeat a couple times to ensure proper system operation prior to installing the product and weekly after installation.
If the alarm panel and wireless receiver are properly communicating with the float switch and wirelss transmitter, disconnect
all power sources before moving on to the steps for installation. If not, call the factory for troubleshooting assistance.
Alarm Systems
Control Panels
Alderon Industries - Hawley, MN | 218.483.3034 | [email protected] | alderonind.com
2
Indoor Components
Indoor Mounted Wireless Receiver
1
Indoor Mounted Alarm Panel/Power Supply
2
Alarm Features:
▪ Alarm Buzzer
▪ Green Power and Red Alarm LEDs
▪ Auxiliary Contacts
▪ Auto Reset Function
Float Switches
™
4
3
Leak Detection Systems
5
(actual riser not included)
Outdoor Components
Wireless Transmitter with
3
Mounting Screws
Float Switch
4
4-Foot Post and 2" Riser
5
Connection Kit
(7992 only)
(Actual Riser Not Included)
P/N: 101985
Page 2 of 6