eControls C365T21WF Installer And User Manual - Seite 6

Blättern Sie online oder laden Sie pdf Installer And User Manual für Thermostat eControls C365T21WF herunter. eControls C365T21WF 13 Seiten.

eControls C365T21WF Installer And User Manual

INSTALLER OPTIONS

Option
Description
01
Equipment Type
02
Reversing Valve (Only displayed if HP selected)
03
Compressor Stages
04
Heating Stages
05
Fan Operation. (Only displayed if GE selected)
06
Compressor Minimum Off Time (minutes).
07
Gas Heating Minimum Off Time (minutes).
08
Minimum Run Time (minutes).
09
On-Off Temperature Differential
o
0 Cool On 1 above setpoint, Off at setpoint. Heat On1 below setpoint, Off at setpoint.
o
1 Cool On 1 above setpoint, Off .5 below setpoint. Heat On1 below setpoint, Off .5 above setpoint.
o
2 Cool On 1 above setpoint, Off 1 below setpoint. Heat On1 below setpoint, Off 1 above setpoint.
10
Smart Recovery.
11
Vacant Heating Setpoint.
12
Vacant Cooling Setpoint.
13
Calibrate Living Area Sensor
14
Calibrate Sleeping Area Sensor.
15
Airflow Update Time
16
Night Level LCD Backlight
17
Airflow Control
18
User (Manual) Airflow Control Enabled
19
Up Stage Time
Maximum Airflow in Heating to the Sleeping Space.
20
Maximum Airflow in Cooling to the Sleeping Space.
21
Maximum Airflow in Heating to the Living Space.
22
Maximum Airflow in Cooling to the Living Space.
23
Maximum Temperature Difference Between
24
Sleeping and Living Spaces.
Factory Restore
25
ACCESSING INSTALLER OPTIONS
To access the Installer Options,
TOUCH
HOLD
the hidden Enter key for 7 seconds until
the first Option appears on the screen.
Sleeping
Airflow %
Schedule
Living
Day
Tu
AM
MENU
MODE
TOUCH
and
The hidden BACK
for 7 seconds to access the
key can be used to
Installer Options.
return to previous
options.
INSTALLER SECTION
Display
o
o
V A C
V A C
C A L
C A L
BL + Night
HAF + Heat
CAF + Cool
HAF + Heat
CAF + Cool
and
Press the touchscreen with your fingertip
!
only, using a firm touch. Do not use a sharp
object such as a pen or pencil.
!
The NEXT key is used to display the next
option.
Cool
The ENTER key is used to save options and
Set To
!
return to normal thermostat operation.
Living
COOL
The hidden BACK key is used to return to
!
SYSTEM
previous options and is located to the left of
the NEXT key.
AUTO
FAN
HOLD
this key
Range
GE or HP
rEV
O or b
CPr
0 or 1 (GE), 0, 1 or 2 (HP)
HtG
0, 1 or 2
FAn
GA(Down) or EL(Up)
0 to 9
COt
HOt
0 to 9
r n t
0 to 9
o
O O
0, 1 or 2
o
o
o
o
S r
0n(Up) or Off(Down)
+Heat
44 to 75F
+Cool
74 to 95F
+/- 5F
+/- 5F
AFt
1 to 20 minutes
On(Up) or Off(Down)
AFC
On(Up) or Off(Down)
UAC
On(Up) or Off(Down)
5 to 30 minutes
USt
100 to 160%
100 to 160%
100 to 160%
100 to 160%
dIF
0 to 100
Fr
No or Yes
Page 6 of 12
Default
GE
O
1(GE) 2(HP)
1
GA
2
0
2
1
o
Off
65F
80F
na
na
2
On
On
On
10
160%
150%
160%
150%
2
No
01 Selecting the Equipment Type
Factory Default: GE. Range: GE or HP
This option is used
to select gas/electric
or heat pump
equipment.
Use the UP/DOWN
keys to select
gas/electric (GE) or heat pump (HP).
Touch NEXT or ENTER.

02 Reversing Valve

(Only displayed if Heat Pump equipment,
HP is selected in Option 01)
Factory Default: O. Range: o or b
This option is used
to select an O or B
type reversing valve.
Use the UP/DOWN
keys to select o for
O-Type or b for B-Type.
Touch NEXT or ENTER.
Set To
na
Option
NEXT
ENTER
Option
NEXT
ENTER