Armstrong Air RP14AC Series Handbuch für Installation und Wartung - Seite 9
Blättern Sie online oder laden Sie pdf Handbuch für Installation und Wartung für Klimagerät Armstrong Air RP14AC Series herunter. Armstrong Air RP14AC Series 13 Seiten.
system charge, evacuate to 500 microns, and weigh in
refrigerant to nameplate charge. It is critical that the exact
charge is re-installed. Failure to comply will compromise
system performance.
If unit performance is still questionable, check for
refrigerant related problems, such as blocked coil or
circuits, malfunctioning metering device or other system
components.
Model
Superheat +/- 3°
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
Based on outdoor ambient temperature of 82°F, and indoor
entering air of 80°F db, 67°F wb.
Table 4. Air Conditioner Unit Cooling System
Performance Values
Model
Superheat +/- 3°
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
Based on outdoor ambient temperature of 82°F, and indoor
entering air of 80°F db, 67°F wb.
Table 5. Heat Pump Cooling System Performance
Model
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
Based on outdoor ambient temperature of 47°F, and indoor
entering air of 70°F db.
Table 6. Heat Pump Heating System Performance
507296-01
Suction
Liquid
Subcooling +/- 2°
10
14
13
12
14
17
Suction
Liquid Subcooling
+/- 2°
18
16
14
9
8
5
Values
Liquid Subcooling +/- 2°
25
15
11
22
24
28
Values
Before performing maintenance operations on the
system, shut off all electrical power to the unit. Turn off
accessory heater power switch if applicable. Electrical
shock could cause personal injury or death.
Periodic inspection and maintenance normally consists of
changing or cleaning the filters and cleaning the outdoor
coil. On occasion, other components may also require
cleaning.
Filters
Filters are not supplied with the unit. Inspect once a month.
Replace disposable or clean permanent type as necessary.
Do not replace permanent type with disposable.
Motors
Indoor and outdoor fan and vent motors are permanently
lubricated and require no maintenance.
Some models may be equipped with a permanent magnet,
constant torque indoor blower motor. These motors remain
energized and are controlled by 24V signals. For high
static applications, use tap 3 for cooling speed and tap
5 for heating speed. Refer to the heater install label for
limitations to blower tap selection on heating speeds.
Outdoor Coil
Dirt and debris should not be allowed to accumulate on
the outdoor coil surface or other parts in the air circuit.
Cleaning should be as often as necessary to keep the coil
clean. Use a brush, vacuum cleaner attachment, or other
suitable means. If water is used to clean the coil, be sure
the power to unit is shut off prior to cleaning. Care should
be used when cleaning the coil so that the coil fins are not
damaged.
Issue 1650
Maintenance
WARNING
Page 9 of 13