Distech LonWorks ECL-400 Series Installationshandbuch - Seite 9

Blättern Sie online oder laden Sie pdf Installationshandbuch für Controller Distech LonWorks ECL-400 Series herunter. Distech LonWorks ECL-400 Series 17 Seiten.

Distech LonWorks ECL-400 Series Installationshandbuch

Output Wiring

Before connecting an output device (actuator, relay, etc.) to the controller, refer to the datasheet and installation
guide of the equipment manufacturer.
£
For a wire length less than 75' (23m) long, either a shielded or unshielded 18AWG wire may be used.
£
For a wire length up to 200' (61m) long, a shielded 18AWG wire is recommended.
£
The shield of the wire should be grounded on the controller side and the shield length should be kept as short
as possible.
£
For relay outputs (DOx); select appropriately-sized wiring suitable to the current load.
£
To measure the state of a triac output, an external load must be connected.
Table 3 shows the ECL-203, ECL-300, ECL-400, and ECL-600 Series controller Output and Jumper support. Table 4 shows the available output wiring
methods.
Controller
ECL‑203
ECL‑300
ECL‑4x0 Series
ECL‑4x3 Series
ECL‑600 Series
Control Output Type
£
Discrete 0 or 12VDC digital, Pulse, or PWM output controlling
a 12VDC relay. Maximum 60 mA (minimum load resistance
200Ω).
£
Current 0 to 20mA universal output & jumper configuration
£
For ECL-300, ECL-400, and ECL-600 Series only
£
For jumper location, see
tion
[pg. 6].
£
Linear 0 to 10VDC digital to analog output.
£
0 to 10VDC voltage output controlling an analog actuator that
is powered by an external 24VAC power source.
£
24VAC externally-powered triac output controlling a floating
1
actuator
.
£
Ensure that the external power supply is grounded as shown.
£
24VAC controller-powered triac output controlling a relay
line and neutral switching.
£
Ensure that the transformer's secondary winding is grounded
as shown.
Digital (Triac) Outputs
5
0
0
8
0
Table 3: Controller Output Support
Jumper Identification and Configura-
Universal Outputs
Output Designation
UOx
UOx
UOx
UOx
DOx
1
with
DOx
0 to 10VDC/0 to 20mA
3
8
12
4
12
Output Connection Diagram
UOx
From
Digital
Output
COM
UOx
0-10V
From Digital-To-
Analog Output
0-20mA
COM
JUMPER
SETTING
From Digital-
UOx
To-Analog
Output
COM
From Digital-
UOx
To-Analog
Output
COM
24VAC
Cy
DOy
Cx
24VAC
DOx
Line Switching
Fuse: 4A Max.
Fast Acting
24VAC
AC
24VAC
24VCOM
Transformer
Controller
Electrical
System Ground
DOx
A2
Load
Cx
A1
24VAC Relay
Jumper
A1
A2
12VDC Relay
0-20mA
Common
0-10V
Common
Actuator
0-10V
~ or +
or -
Actuator
~
~
Neutral Switching
Fuse: 4A Max.
Fast Acting
24VAC
AC
24VAC
24VCOM
Transformer
Controller
Electrical
System Ground
DOx
A2
Load
Cx
A1
24VAC Relay
9 / 16