Distech Controls Allure UNITOUCH Gebrauchsanweisung

Mounting Instructions

The Allure UNITOUCH has been specially designed for easy installation. However, certain conditions apply when choosing a suitable location for the de-
vice:
£
Install the device in a location of average temperature and approximately 1.5 m (5 ft) above the floor
£
The device should be installed approximately 15cm (6") from a corner to provide sufficient access to the faceplate release tabs.
£
The device should not be installed on an exterior wall.
£
The device should not be installed near a heat source.
£
The device should not be installed near an air discharge grill.
£
The device should not be installed in a place where it can be affected by the sun.
£
Install the device in an area that provides proper device ventilation. Nothing must restrain air circulation to the device.
The Allure UNITOUCH has not been designed for outdoor use.
Mounting hardware with a separate sub-base is provided with the device for installation on drywall or on an electrical junction box.
Electrical Junction Box Installation Procedure
The Allure UNITOUCH sensor can be mounted in most American, European or Asian style electrical junction box using screws.
1. Remove the front cover of the device:
– Remove the security screw
– Using an appropriately sized tool, press in the two (2) release tabs on the sides of the device and pull the front cover out from the bottom. See
Figure 2 [pg. 3]
for security screw and release tab locations.
2. Pull all cables 15cm (6") out of the wall and insert them through the central hole of the back plate.
3. Ensure the EOL jumpers are correctly set and that the protocol toggle is in the SUBNET (default) position. See
switch component locations.
4. Make sure that the mounting surface is flat and clean.
5. Screw the back plate onto the electrical junction box.
6. Plug the wire(s) into the connector(s). Gently push excess wiring back into the wall.
7. Reattach the front plate and make sure it clips tightly into place. Tighten the security screw.
Wall Mounting Installation Procedure
Figure 4:
UNITOUCH backplate screw positions
The Allure UNITOUCH can be mounted on drywall using the supplied screws.
1. Remove the front cover of the device:
– Remove the security screw
– Using an appropriately sized tool, press in the two (2) release tabs on the sides of the device and pull the front cover out from the bottom. See
Figure 2 [pg. 3]
for security screw and release tab locations.
2. Pull all cables 15cm (6") out of the wall and insert them through the central hole of the back plate.
3. Ensure the EOL jumpers are correctly set and that the protocol toggle is in the SUBNET (default) position. See
switch component locations.
4. Align the back plate with the wall and mark the location of the mounting holes on the wall. Make sure to orient the proper end of the back plate facing
upwards.
4 / 7
Figure 3 [pg. 3]
for jumper and dip
Figure 3 [pg. 3]