Distech Controls PS-2AEULDP Series Installationshandbuch - Seite 2
Blättern Sie online oder laden Sie pdf Installationshandbuch für Transmitter Distech Controls PS-2AEULDP Series herunter. Distech Controls PS-2AEULDP Series 5 Seiten. Ultra low pressure transmitter
Mounting Instructions
The transmitter mounts on a vertical surface using the two integrated mounting holes. Ensure there is enough space around the unit to connect the
pressure tubing without kinking and avoid locations with severe vibrations or excessive moisture. The two mounting holes will facilitate a #10 size screw
(not supplied). See Figure 2. It should be mounted on a vertical surface with the pressure ports on the bottom and the cable entrance on the left.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the bottom of the enclosure and at the same time pulling
on the cover, as illustrated in Figure 3.
A 1/2" NPT threaded connection hole is provided on the side of the enclosure. Screw the EMT connector or cable gland connector in until tight. See Figure
4. It is recommended that weatherproof conduit or cable gland fittings be used. Optional 1/2" NPT to M16 thread adapter and cable gland fitting installation,
see Figure 4.
Make wiring connections as per the "Wiring" illustrations. Swing door closed until securely latched. For added security, 2 screws are provided that may be
installed in the integrated screw tabs. See Figure 5.
2/5
Figure 2: Enclosure Mounting.
Figure 3: Opening enclosure.
Figure 4: Cable installation.
Figure 5: Door security latch.