esera automation 20002 Benutzerhandbuch - Seite 2
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Zubehör esera automation 20002 herunter. esera automation 20002 4 Seiten. Rain sensor 12v
3
Settings
Output signal transmitter (optional): A passive piezo signal
transmitter can be connected to the connector strip (pin BUZ and
GND). The status of the signal (acoustic signal at dry or wet) can be
set with jumper S1-S2 or S2-S3. In the default position S2-S3 the
signal transmitter is inactive when it rains.
Switching behavior: The switching behavior of the relay (energised
or de-energised in rain) can be set with the jumper of T1-T2 or T2-
T3. In the factory setting the jumper T1-T2 is plugged in and the relay
picks up when the sensor surface becomes wet.
Heating: The sensor surface is heated if the bridge of HZ1-HZ2 is
plugged in. To ensure faster drying and for use below freezing, the
heater should be switched on. The heater can be switched off to
detect fog.
Sensitivity setting: The sensitivity of the humidity signal can be influenced at the potentiometer. A higher sensitivity
is achieved by turning the potentiometer axis counterclockwise (right = high sensitivity, left = low sensitivity). The
middle position is most suitable for normal rain signaling. Note that there is no function at the end stops!
Loosen the cover screws of the sensor, unlock the plug connector of the sensor cable and put the cover aside first.
This will prevent damage to the sensor connection cable during the following steps. Mount the cable gland to the
housing.
4
Technical data
Temperature measurement
Operating voltage
12V DC/AC +10%
Current consumption
60 mA
Heating 80-300mA (PTC)
Measurement method
electrolytic AC voltage
measurement
Load on contacts
max. 30V DC / 4 A
Connection terminals
0,5mm - 1,5mm2
Clamp with wire protection
Dimensions
80 mm x 82 mm x 58 mm
Distance between
Horizontal: 50 mm Vertical: 70
mounting holes
mm, Diameter: 4,3 mm
Cable inlet
M16
Housing
ABS, Protection system IP54
EMC-compatibility
89/336/EWG
Interference emission
EN 61000-6-3
Interference immunity
EN 61000-6-1
Package contents
Rain detector in housing, PG
cable gland / blind cover, cover
screws and documentation
optional extras
Wall/pole bracket
Best. No. REGME-WAHA
The technical data are subject to change without notice!
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Pin assignment
Terminal block
REL NC
REL NO
REL CO
AC/DC
AC/GND
plug bridges
Configuration
1
S3
2
S2
3
S1
4
GND Ground Signal transmitter
5
BUZ
6
T3
7
T2
8
T1
9
HZ1
10 HZ2
Factory setting: S3-S2
20002 V2.0 R1.0 Manual
Switching contact NC contact
Switching contact N/O contact
Switching contact fixed pole
operating voltage AC or +12V DC +10%
Operating voltage AC or 0V
Switching behaviour of signal transmitter
(dry)
Center contact to S3, S1
Switching behaviour of signal transmitter
(wet)
Output signal transmitter
Switching behaviour relay (dry)
Center contact to T3, T1
Switching behaviour relay (wet)
Heating
Heating
T1-T2
HZ1-HZ2
Page 2 of 4