dixell CoolMate XLR170C Installations- und Betriebsanweisungen - Seite 18

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanweisungen für Controller dixell CoolMate XLR170C herunter. dixell CoolMate XLR170C 20 Seiten. Cool mate

dixell CoolMate XLR170C Installations- und Betriebsanweisungen

16. DEFAULT SETTING VALUES

Label
Name
REGULATION
Set
Set point
Hy
Differential
LS
Minimum set point
US
Maximum set point
OdS
Outputs activation delay at start up
cco
Compressor configuration
AC
Anti-short cycle delay
Ac1
Second compressor start up delay
CCt
Compressor ON time during fast freezing
COn
Compressor ON time with faulty probe
COF
Compressor OFF time with faulty probe
CH
Kind of action
DISPLAY
CF
Temperature measurement unit
rES
Resolution (integer/decimal point)
Lod
Local display
DEFROST
tdF
Defrost type
EdF
Defrost mode
SdF
Set point for SMART DEFROST
dtE
Defrost termination temperature (1°Evaporator)
dtS
Defrost termination temperature (2°Evaporator)
IdF
Interval between defrost cycles
MdF
(Maximum) length for 1° defrost
MdS
Maximum) length for 2° defrost.
dFd
Displaying during defrost
dAd
MAX display delay after defrost
dSd
Start defrost delay
Fdt
Draining time
dPO
First defrost after start up
dAF
Defrost delay after fast freezing
dFP
End defrost probe for first evaporator
dSP
End defrost probe for second evaporator
FANS
FnC
Fans operating mode
Fnd
Fans delay after defrost
FSt
Fans stop temperature
FAP
Fan probe selection
ALARMS
ALC
Temperature alarms configuration
ALU
MAXIMUM temperature alarm
ALL
minimum temperature alarm
AFH
Temperature alarm and fan differential
ALd
Temperature alarm delay
dAO
Delay of temperature alarm at start up
EdA
Alarm delay at the end of defrost
dot
Delay of temperature alarm after closing the door
dOA
Open door alarm delay
rrd
Regulation restart after door open alarm
tBA
Alarm relay silencing
nPS
Pressure switch activation number
ANALOGUE INPUTS
Ot
Thermostat probe calibration
OE
Evaporator probe calibration
O3
Auxiliary probe calibration
P2P
Evaporator probe presence
P3P
Auxiliary probe presence
Pbr
Regulation probe selection
1592017000 XLR 130-170 GB r2.0 23.03.2015
Range
LS÷US
0,1÷25,5 °C / 1÷45°F
-50,0°C÷SET / -58°F÷SET
SET ÷ 110°C / SET ÷ 230°F
0÷255 min.
SE; AL
0÷30 min.
0÷255 sec.
0 ÷ 23h 50 min.
0÷255 min.
0÷255 min.
CL; Ht
°C ÷ °F
in ÷ de
P1 ÷ 1r2
rE, rT, in
rtc, In, Sd
-30 ÷ +30°C / -22÷+86°F
-50,0÷110°C /-58÷230°F
-50,0÷110°C / -58÷230°F
1÷120h
0÷255 min.
0÷255 min.
rt, it, SEt, dEF, dEG
0÷255 min.
0÷99 min.
0÷60 min.
n ÷ y
0 ÷ 23h 50 min.
nP; P1, P2, P3
nP; P1, P2, P3
C-n, C-y, O-n, O-y
0÷255 min.
-50,0÷110°C / -58÷230°F
nP; P1, P2, P3
rE÷Ab
-50,0÷110°C/-58÷230°F
-50,0÷110°C/ -58÷230°F
0,1÷25,5 °C/ 1÷45°F
0÷255 min.
0 ÷ 23h 50 min.
0÷255 min.
0÷255 min.
0÷254 min.,nu
y ÷ n
y ÷ n
0÷15
-12,0÷12,0°C / -21÷21°F
-12,0÷12,0°C / -21÷21°F
-12,0÷12,0°C / -21÷21°F
n ÷ y
n ÷ y
P1, P2, P3, 1r2
XL130 - XLR170
XLR130
XLR170
Level
3.0
-5.0
---
2.0
2.0
Pr1
-10.0
-30,0
Pr2
20.0
20.0
Pr2
0
0
Pr2
SE
SE
Pr2
1
1
Pr1
0
0
Pr2
0.0
0.0
Pr2
15
15
Pr2
30
30
Pr2
cL
- - -
Pr2
°C
°C
Pr2
dE
dE
Pr1
P1
P1
Pr2
- - -
rE
Pr2
in
in
Pr2
0
0
Pr2
8.0
8.0
Pr2
- - -
8.0
Pr2
8
8
Pr1
20
20
Pr1
-
0
Pr2
it
it
Pr2
30
30
Pr2
- - -
0
Pr2
- - -
0
Pr2
n
n
Pr2
2
2.0
Pr2
- - -
P2
Pr2
- - -
nP
Pr2
O-n
O-n
Pr2
10
10
Pr2
2.0
2.0
Pr2
nP
P2
Pr2
rE
rE
Pr2
10.0
10.0
Pr1
10.0
10.0
Pr1
2.0
2.0
Pr2
15
15
Pr2
1.3
1.3
Pr2
30
30
Pr2
15
15
Pr2
15
15
Pr2
y
y
Pr2
y
y
Pr2
0
0
Pr2
0
0.0
Pr1
- - -
0.0
Pr2
0
0.0
Pr2
- - -
y
Pr2
n
n
Pr2
P1
P1
Pr2
18/20