dixell XR20C Installations- und Betriebsanleitung - Seite 2

Blättern Sie online oder laden Sie pdf Installations- und Betriebsanleitung für Thermostat dixell XR20C herunter. dixell XR20C 2 Seiten. Thermostat with off cycle defrost

dixell XR20C Installations- und Betriebsanleitung
Dixell
Installing and Operating Instructions
COF
Compressor OFF time with faulty probe:
(0÷255 min) time during which the compressor is OFF
in case of faulty thermostat probe. With COF=0
compressor is always active.
DISPLAY
CF
Temperature measurement unit:
Celsius; °F= Fahrenheit. WARNING: When the
measurement unit is changed the SET point and the
values of the parameters Hy, LS, US and Ot have to be
checked and modified if necessary).
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows the
decimal point displaying.
DEFROST
dtE Defrost termination temperature: (-50÷50 °C/
-58÷122°F) (Enabled only when P2P=y) sets the
temperature measured by the evaporator probe, which
causes the end of defrost.
IdF Interval between defrost cycles: (1÷120h) Determines
the time interval between the beginning of two defrost
cycles.
MdF Length for defrost: (0÷255min) It sets the defrost
duration.
dFd Temperature displayed during defrost: (rt = real
temperature; it = temperature at defrost start; SEt = set
point; dEF = "dEF" label)
dAd MAX display delay after defrost: (0÷255min).
Sets the maximum time between the end of defrost and
the restarting of the real room temperature display.
DIGITAL INPUT
i1P Digital input polarity: oP: the digital input is activated
by opening the contact; CL: the digital input is activated
by closing the contact.
did: (0÷255 min) door open signalling delay
odc Compressor status when open door:
no=Digital Input not used CPr= Compressor OFF.
OTHER
rEL Software release for internal use.
Ptb Parameter table index: readable only. For internal use.
7. DIGITAL INPUT
7.1 DIGITAL INPUTS POLARITY
The digital input polarity depends on the "i1P" parameter.
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact
8. INSTALLATION AND MOUNTING
Instrument XR20C shall be mounted on panel, in a 29x71
mm hole, and fixed using the special brackets supplied.
To obtain an IP65 protection grade use the front panel rubber
gasket (mod. RG-C) as shown in figure.
The temperature range allowed for correct operation is 0÷60
°C. Avoid places subject to strong vibrations, corrosive
gases,
excessive
dirt
or
moisture.
recommendations apply to probes. Let air circulate by the
cooling holes.
9. ELECTRICAL CONNECTIONS
The instruments are provided with screw terminal block to
connect cables with a cross section up to 2,5 mm
resistant cables have to be used. Before connecting cables
make sure the power supply complies with the instrument's
XR20CE2probecooling
requirements. Separate the probe cables from the power
supply cables, from the outputs and the power
connections. Do not exceed the maximum current allowed
on each relay, in case of heavier loads use a suitable
external relay.
°C =
9.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to
prevent damages due to casual liquid infiltration. It is
recommended to place the probe away from air streams to
correctly measure the average room temperature.
10. HOW TO USE THE HOT KEY
10.1 HOW TO PROGRAM A HOT KEY FROM THE
INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the "Hot key" and
push o key; the "uPL" message appears followed a
The word "End"
3.
Push "SET" key and the End will stop being displayed.
4.
Turn OFF the instrument remove the "Hot Key", then
turn it ON again.
NOTE: the "Err" message is displayed for failed
programming. In this case push again o key if you want to
restart the upload again or remove the "Hot key" to abort the
operation.
10.2 HOW TO PROGRAM AN INSTRUMENT
USING A HOT KEY (DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed "Hot Key" into the 5 PIN
receptacle and then turn the Controller ON.
3.
Automatically the parameter list of the "Hot Key" is
downloaded into the Controller memory, the "doL"
message is blinking followed a by "End".
4.
After 10 seconds the instrument will restart working
with the new parameters.
5.
Remove the "Hot Key".
NOTE the message "Err" is displayed for failed programming.
In this case turn the unit off and then on if you want to restart
the download again or remove the "Hot key" to abort the
operation.
11. ALARM SIGNALS
Message
"EE"
Data or memory failure
"P1"
Room probe failure
"P2"
2
probe failure
nd
"dA"
Door open
11.1 ALARM "EE"
The instrument is provided with an internal check verifying
memory integrity. Alarm "EE" flashes when a failure in the
internal memory is detected. In such case call the service.
11.2 ALARM RECOVERY
Probe alarm "P1 & P2" start some seconds after the fault in
the related probe; it automatically stops some seconds after
the probe restarts normal operation. Check connections
before replacing the probe.
Alarm dA will recover as soon as the digital input is disabled.
12. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR20C frontal 32x74 mm; depth 60mm;
Mounting
XR20C panel mounting in a 71x29mm panel cut-out
Protection: IP20.
Frontal protection:
XR20C IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block ≤ 2,5 mm
resistant wiring.
The
same
Power supply: according to the model: 12Vac/dc, ±10%;
24Vac/dc, ±10%; 230Vac ±10%, 50/60Hz, 110Vac ±10%,
50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 2 NTC probes. 1 Digital input
2
. Heat-
Relay outputs
Compressor:
SPST relay 16FLA/96LRA
Cause
Output
Output according to par.
"Con" and "COF"
Output unchanged
Regulation restarts
heat-
2
XR20C
Data storing: on the non-volatile memory (EEPROM).
Kind of action: 1B.
Pollution grade: normal
Software class: A.
Operating temperature: 0÷60 °C.
Storage temperature: -25÷60 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
13. CONNECTIONS
13.1 XR20C: 16FLA COMPRESSOR
4 5
6
7
8
Supply
Comp
120V~
Line
120Vac supply: connect to the terminals 7 and 8.
OPTIONAL:
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
230Vac supply: connect to the terminals 7 and 8.
14. DEFAULT SETTING VALUES
Label
Name
Set Set point
Hy Differential
LS Minimum set point
US Maximum set point
Ot Thermostat probe calibration
P2P 2
nd
probe presence
OE 2
probe calibration
nd
OdS Outputs delay at start up
AC Anti-short cycle delay
COn Compressor ON time with faulty
probe
COF Compressor OFF time with faulty
probe
CF Temperature measurement unit
rES Resolution
dtE Defrost end temp
IdF Interval between defrost cycles
MdF (Maximum) length for defrost
dFd Displaying during defrost
dAd MAX display delay after defrost
i1P Digital input polarity
did Digital input alarm delay
odc Compressor status with open door:
rEL Software release
Ptb Map code
Hidden parameters
Dixell s.r.l. Z.I. Via dell'Industria, 27
32010 Pieve d'Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail: [email protected] - http://www.dixell.com
9 10 11 12
Hot Key
Range
°C/°F
LS÷US
3/37
0,1÷25.5°C/
2/4
1÷ 45°F
-50°C÷SET/
-40/
-58°F÷SET
- 40
SET÷150°C/
110/
SET ÷ 230°F
230
-12÷ 12°C /
0/0
-21 ÷ 21°F
Y/N
Y
-12÷12°C /-
120÷120°F
0÷255 min
0
0 ÷ 50 min
1
0 ÷ 255 min
15
0 ÷ 255 min
30
°C ÷ °F
°C/°F
in ÷ dE
dE/-
-50 ÷ 50 °C
46
1 ÷ 120 hour
8
0 ÷ 255 min
20
rt, it, SEt,
it
DEF
0 ÷ 255 min
30
oP=opening;
cL
CL=closing
0÷255min
5
No=No Digital
no
input used.
CPr; =
Compressor
off
--
-
--
-
2/2