5.
Battery operating time depends on the capacity (amp hours) of the batteries being used
and the amount of power being used (wattage). The calculation for determining
operating time is:
[ battery capacity (AH) X battery output voltage (V) ] / power being used (W)
Example: A 12V 200Ah battery with a 600W power load has 4 hours of operating time
(200 X 12 / 600 = 4)
6.
The soft start technology built into this inverter protects the unit from outputting too
much AC voltage at once by gradually increasing the amount of power pushed out.
To make sure that you're utilizing this feature, turn on the appliance being used before
turning on the inverter. This is especially necessary for products that use an inductive
load or electrical motor.
7.
The electrical waveform output of this inverter is a pure sine wave, which has the
same quality as utility and/or domestic power. This type of waveform is suitable for
most all electrical devices, appliances and tools. This pure sine wave unit provides
more capabilities than modified sine wave inverters, because it is a cleaner form of
power. The pure sine wave also effectively reduces the noise produced while using
appliances.
8.
1. Input under-voltage alarm: When the input DC voltage is lower than 10.6V, the buzzer
will whistle intermittently to remind that the inverter will go into under voltage protection.
Pay attention to save the data if you are using computer.
2 .Under voltage protection: The inverter will automatically shut down when the input DC
voltage is lower than 10V.The buzzer will whistle continuously and the green light is off red
light on. Please turn off the inverter and use it after recharge the battery.
3. Over voltage protection: The inverter will automatically shut down when the input DC
voltage is higher than 16V.The buzzer will whistle continuously and the switch indicator
light is on. Please turn off the inverter and adjust the input voltage to the admissible range.
4. Overload protection: The inverter will automatically shut down when the load power is
higher than the rated power. The buzzer will whistle continuously. Turn off the inverter and
resume to normal operation after taking away the excessive load.
5. Thermal protection: The unit will get hot during operation. If the temperature is higher
than 65°C, the inverter will automatically shut down. Then the buzzer will whistle
continuously and the green light is off,red light is on. Please turn off the inverter, and
continue using it after the temperature goes back to normal temperature naturally.
Meanwhile find out the factors caused the fault, such as ventilation, ambient temperature,
vent, load power and so on.