Installing iPrism on a Rack
Choosing a Setup Location
Leave enough clearance in front of the rack to enable you to open the front door completely (~25 inches).
Leave approximately 30 inches of clearance in the back of the rack to allow for sufficient airflow and ease in servicing.
This product is for installation only in a Restricted Access Location (dedicated equipment rooms, service closets and the like).
This product is not suitable for use with visual display workplace devices according to §2 of the German Ordinance for Work with Visual Display Units.
Warnings and Precautions
Rack Precautions
Ensure that the leveling jacks on the bottom of the rack are fully extended to the floor, with the full weight of the rack resting upon them.
In single rack installation, stabilizers should be attached to the rack.
In multiple rack installations, the racks should be coupled together.
Always make sure the rack is stable before extending a component from the rack.
You should extend only one component at a time — extending two or more simultaneously may cause the rack to become unstable.
Server Precautions
Ensure you are familiar with electrical and general safety precautions.
Determine the placement of each component in the rack before you install the rails (click
Install the heaviest server components on the bottom of the rack first, then work up.
Use a regulating uninterruptible power supply (UPS) to protect the server from power surges, voltage spikes and to keep your system
operating in case of a power failure.
Allow the hot plug SATA drives and power supply modules to cool before touching them.
Always keep the rack's front door and all panels and components on the servers closed when not servicing to maintain proper cooling.
Rack Mounting Considerations
Ambient Operating Temperature
If installed in a closed or multi-unit rack assembly, the ambient operating temperature of the rack environment may be greater than the
ambient temperature of the room. Therefore, consideration should be given to installing the equipment in an environment compatible
with the manufacturer's maximum rated ambient temperature (Tmra).
Reduced Airflow
Equipment should be mounted into a rack so that the amount of airflow required for safe operation is not compromised.
Mechanical Loading
Equipment should be mounted into a rack so that a hazardous condition does not arise due to uneven mechanical loading.
Circuit Overloading
Consideration should be given to the connection of the equipment to the power supply circuitry and the effect that any possible
overloading of circuits might have on overcurrent protection and power supply wiring. Appropriate consideration of equipment
nameplate ratings should be used when addressing this concern.
Reliable Ground
A reliable ground must be maintained at all times. To ensure this, the rack itself should be grounded. Particular attention
should be given to power supply connections other than the direct connections to the branch circuit (e.g., the use of power strips, etc.).
here
for instructions on how to install rails).