Altronic DSG-1611DUPS Service-Bulletin
Blättern Sie online oder laden Sie pdf Service-Bulletin für Messgeräte Altronic DSG-1611DUPS herunter. Altronic DSG-1611DUPS 2 Seiten. “custom” label instructions
SERVICE BULLETIN
"CUSTOM" LABEL INSTRUCTIONS
DSG-1611DUPS & DSG-1692DUS
For the DSG-1611 and Channel 1 of the DSG-1692:
Set Register 40030 to 1 (custom label)
Set Registers 40031-40038 to desired characters as follows.
Each label register holds two ASCII characters like so:
40031 = character 1 & 2
40032 = character 3 & 4
40033 = character 5 & 6
40034 = character 7 & 8
40035 = character 9 & 10
40036 = character 11 & 12
40037 = character 13 & 14
40038 = character 15 & 16
When building a label, first write out how you want it to look
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P R E
C A T
Next, lookup the ASCII codes that correspond to those letters
P=50H (hex) R=52H E=45H <space>=20H C=43H A=41H T=54H
Now make hex pairs to fill the registers. Notice how
8
so character
and all remaining characters should be
40031 = 5052H
40032 = 4520H
40033 = 4341H
40034 = 5400H
40035 = 0000H
40036 = 0000H
40037 = 0000H
40038 = 0000H
Next, write these values to the registers. If using Altronic ModbusTool,
first convert the hex numbers to decimal like so:
40031 = 20562
40032 = 17696
40033 = 17217
40034 = 21504
40035 = 0000H
40036 = 0000H
40037 = 0000H
40038 = 0000H
The Custom Label is now programmed.
CONTINUED
T
7
ends in character
0
.
NUMBER 505
3/23/07
www.altronicinc.com
330-545-9768
1 of 1