Power Supply Board
Terminal Legend
L, G, N
+ DC –
AC FAIL
NC, C, NO
BAT FAIL
NC, C, NO
– BAT +
MOM5 - Output Module
Terminal Legend
– DC INPUT +
TRIGGER
– INPUT +
NEG. 1
through NEG. 5
POS. (+) DC
OUTPUT
(ALARM) 1-5
POS. (+) DC
OUTPUT
(STAND-BY) 6-10
NC, C, NO
DRY OUTPUT
NC, C, NO
POWER FAIL
- 10 -
Terminal Identification Tables:
Function/Description
Connect 220VAC, 50/60Hz to these terminals: L to hot, N to neutral.
AL300M220 - 12VDC/24VDC @ 2.5A to MOM5 board.
AL400M220 - 12VDC @ 4A or 24VDC @ 3A to MOM5 board.
AL600M220 - 12VDC/24VDC @ 6A to MOM5 board.
AL1012M220 - 12VDC @ 10A to MOM5 board.
AL1024M220 - 24VDC @ 10A to MOM5 board.
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay
normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or
brownout fail is reported within 1 minute of event. To delay reporting for up to 6 hrs.,
cut "AC delay" jumper and reset power to the unit.
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported
within 5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.
Stand-by battery connections.
AL300XB2V, AL400XB2V, AL600XB220 and AL1012XB220 (Power Supply Board)
maximum charge current is 0.7A.
AL1024XB2V (Power Supply Board) maximum charge current is 3.6A.
Function/Description
12VDC or 24VDC from power supply.
Dry normally open [NO] or normally closed [NC] supervised (2.2K EOL resistor) input
trigger. A short or open circuit will transfer power from terminals marked [POS. (+) DC
OUTPUT (STAND-BY)] to terminals marked [POS (+) DC OUTPUT (ALARM)].
Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown
will transfer power from terminals marked [POS. (+) DC OUTPUT (STAND-BY)] to
terminals marked [POS. (+) DC OUTPUT (ALARM)] (e.g. fire alarm control panel
indications circuit).
Supplies constant negative (–) voltage.
Supplies positive (+) voltage when dry trigger input or fire alarm wet trigger input
is applied.
Supplies positive (+) voltage in normal condition. Power is removed when dry trigger
input or fire alarm wet trigger input is applied.
When the MOM5 is triggered the terminals marked [C and NO] will open and the ter-
minals marked [C and NC] will close. This output is used to trigger auxiliary devices.
(e.g. HVAC Shutdown, Elevator Recall etc.). Contact rating 1A @ 28VDC.
Form "C" contacts used for reporting no voltage is present at [– DC INPUT +] terminals.
Under normal conditions, terminals marked [NO and C] are open, [NC and C] are closed.
A loss of power causes terminals marked [NO and C] to close and [NC and C] to open.
Contact rating 1A @ 28VDC.