Arthur Grillo DS200 Installations- und Betriebshandbuch - Seite 8

Blättern Sie online oder laden Sie pdf Installations- und Betriebshandbuch für Zubehör Arthur Grillo DS200 herunter. Arthur Grillo DS200 16 Seiten. Differential pressure sensor

Arthur Grillo DS200 Installations- und Betriebshandbuch

OPERATION

4.4 Electrical connection

P
1.
Unscrew screws of the front cover.
2.
Open front cover.
3.
Use the M16 x 1.5 screw for connecting to terminals.

4.5 Zero adjustment

P
The zero point can be adjusted independently from the menu. For readjusting please use
the small bar magnet and be sure that the device is not in menu mode.
5.
Operation

5.1 Start menu

For operating the menu, unscrew the front cover to reach buttons T1 and T2.
8
Doc.-no.: DS200_01_EN
+17...30 Vdc oder 24 Vac (±15%) Versorgung
Adjustment:
Remove the tubing from the pressure
connections.
Hold the bar magnet (N/S) as shown here
to the zero point adjustment for a short
period of time to activate an internal reed
switch.
The new zero point will be displayed and
stored.
Issue: 05/2017