a-TroniX Parallel Interface Card 6–10 kVA
3. Parallel Function Test
1. The minimum UPS systems in parallel is 2 and the maximum UPS systems in parallel is 4.
Each UPS has been required to have its own parallel kit.
2. After all the installations of parallel kit are done in all the UPS required to be in parallel.
To start only one of the UPS in parallel until the UPS start up is done successfully, then
you may set the working mode of this UPS in parallel in "Parallel Mode". It is required to
set Parallel quantity (2-4) and parallel ID (1-4) and redundancy quantity (default is 0). If
the setting is done successfully, you may turn off this UPS and go for same setting for
other UPS in parallel.
NOTE:
The parallel ID cannot be set the same, for example, if you have 3 UPS in parallel,
you have to set Parallel ID for three different UPS.
3. After settings are done completely, you can start up the UPS in parallel simultaneously
or you can start up one of the other to avoid high inrush current.
4. The input of the UPS in parallel has to be connected together, so as the output of the
UPS in parallel.
Parallel Mode
Parallel Quantity
09/2021
Parallel ID
Redundancy Quantity
Page 7