Altronix AL1042ULADA Anwendungshandbuch - Seite 6

Blättern Sie online oder laden Sie pdf Anwendungshandbuch für Extender Altronix AL1042ULADA herunter. Altronix AL1042ULADA 8 Seiten. Nac power extenders
Auch für Altronix AL1042ULADA: Installationshandbuch (17 seiten), Installationshandbuch (3 seiten), Anwendungshandbuch (8 seiten)

Altronix AL1042ULADA Anwendungshandbuch
Outputs must be programmed independently (OUT1 - OUT4)
Switch Positions
Function
Input to Output
Follower Mode
Temporal
Code 3 Mode
Steady Mode
For the above modes DIP Switch 4 determines which Input controls the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
Note: It is required to control visual notification appliances (strobes) via
Input 1 (IN1) and audible notification appliances (horns) via Input 2 (IN2).
This allows audible notification appliances (horns) and visual notification
appliances (strobes) to be silenced/ deactivated at same time.
The FACP must be capable of a visual annunciation to the silencing status of
the output or zone(s) to which the AL1042/R1042ULADA (NAC Power Extender) is connected.
Function
Amseco
Sync Mode*
®
Gentex
Sync Mode*
Gentex is a registered
trademark of
Gentex Corporation.
®
System Sensor
Sync Mode*
System Sensor is a
registered trademark
of Honeywell.
®
CooperWheelock
Sync Mode*
CooperWheelock is a
registered trademark
of Cooper Wheelock.
*Note: AL1042ULADA, R1042ULADA will only synchronize horns, horn/strobes, and strobes that contain
synchronization capability. The same synchronization mode must be selected for all outputs.
- 6 -
Output Programming Selection Table:
Descriptions
ON
OFF
Output follows signal it receives from the corresponding input (i.e. FACP
1
2, 3
Sync module - maintains synchronization of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
3
1, 2
This mode will accept a steady or a pulsing input.
A steady output signal will be generated.
1, 2, 3
This mode will accept steady or pulsing input.
Sync Mode Selection Table:
Switch Positions
Descriptions
ON
OFF
This mode is designed to work with the Amseco series of horns, strobes,
and horn/strobes to provide a means of synchronizing the Temporal-
1, 3,
2
coded horns, synchronizing the flash timing of the strobe, allowing
4
audible notification appliances (horns) and visual notification appliances
(strobes) to be silenced/deactivated at the same time.
This mode is designed to work with the Gentex
and horn/strobes to provide a means of synchronizing the Temporal-
1, 2,
coded horns, synchronizing the flash timing of the strobe, allowing
3, 4
audible notification appliances (horns) and visual notification appliances
(strobes) to be silenced/deactivated at the same time.
This mode is designed to work with the System Sensor
strobes, and horn/strobes to provide a means of synchronizing the
1, 2, 4
3
Temporal-coded horns, synchronizing the one-second flash timing of the
strobe, allowing audible notification appliances (horns) and visual notifica-
tion appliances (strobes) to be silenced/deactivated at the same time.
This mode is designed to work with the CooperWheelock
horns, strobes, and horn/strobes to provide a means of synchronizing the
2, 3, 4
1
Temporal-coded horns, synchronizing the one-second flash timing of the
strobe, allowing audible notification appliances (horns) and visual notifica-
tion appliances (strobes) to be silenced/deactivated at the same time.
AL842LGK Board
Output DIP Switches
INPUT SELECT
TEMPORAL
STROBE SYNC
IN>OUT SYNC
®
series of horns, strobes,
®
series of horns,
®
series of
42 ULADA Application Guide