Altronix AL642ULADA Installationshandbuch - Seite 2
Blättern Sie online oder laden Sie pdf Installationshandbuch für Extender Altronix AL642ULADA herunter. Altronix AL642ULADA 17 Seiten. Nac power extenders
Auch für Altronix AL642ULADA: Installationshandbuch (17 seiten), Installationshandbuch (16 seiten), Anwendungshandbuch (8 seiten), Anwendungshandbuch (8 seiten)

The Altronix AL642ULADA is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be con-
nected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC
such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support sys-
tem accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A,
Style Z NAC loop circuits. Additionally, a separate 1 amp auxiliary output for 4-wire smoke detectors is available. The 6.5
amp max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5
amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may
be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output).
An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision
for Class A, Style Z and/or Class B, Style W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP
will be notified via the steered input (input 1 or input 2). In addition, there are common trouble output terminals [NC, C,
NO] which are used to indicate general loop/system trouble. A common trouble input is provided for optional [NC] (nor-
mally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be employed and directed to con-
trol supervision and power delivery to any combination of the four (4) outputs.
Agency Listings:
• UL Listed Control Units and Accessories for
Fire Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC 60 Hz, 4 amp.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, X, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• Class 2 Rated power limited outputs.
• 24VDC voltage regulated power limited outputs.
• 6.5 amp max total alarm current.
• 2.5A max current per output.
• Two auxiliary outputs rated at 1 amp each
(1 amp continuous, 1 amp AC disconnect).
• Two (2) outputs may be paralleled for more power on
an indicating circuit (see 42 Application Guide).
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, X, Y or Four (4) Class A,
Style Z or Two (2) Class A, Style Z and Two (2) Class B,
Style W, X, Y (see 42 Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Charging voltage is 26.2-26.4VDC.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when
AC fails.
• Zero voltage drop when switching over to
battery backup.
Supervision:
• AC fail supervision (form "C" contact, 1 amp / 28VDC).
Factory set for 30 seconds with optional 2.5 to 3 hour
delay setting (field selectable).
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
- 2 -
AL642ULADA - NAC Power Extender
Overview:
Specifications:
Supervision (cont.):
• Instant local AC trouble reporting relay
• Battery presence and low battery supervision
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible
• Temporal Code 3, Steady Mode, Input to Output
• Compatible with 24VDC fire panels.
• Output loop supervision directed to input 1 or input 2.
• Signal Circuit Trouble Memory - facilitates quick
• Common trouble input and output for external trouble
• Ground fault detection.
Added Features:
• Unit includes power supply, logic board enclosure,
Enclosure Dimensions and Descriptions:
AL642ULADA
18"H x 14.5"W x 4.625"D
Product Weight:
20 lbs.
(form "C" contact, 1 amp / 28VDC).
(form "C" contact, 1 amp / 28VDC).
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
Follower Mode (maintains synchronization of
notification appliances circuit).
identification of an intermittent/fault (short circuit, open
or ground) which has previously occurred on one or
more signaling circuit outputs. LEDs indicate/identify
which output the fault has occurred.
signals tie-in.
cam lock, and battery leads.
AL642ULADA