CUTLER-HAMMER 24kV Type W-VAC Circuit Breaker
3-4
STORAGE
If the circuit breaker is to be placed in storage,
maximum protection can be obtained by keeping
it packed as shipped. Before placing it in
storage, checks should be made to make sure
that the circuit breaker is free from shipping
damage and is in satisfactory operating
condition.
The circuit breaker is shipped with its contacts
open and closing springs discharged. The
indicators on the front panel should confirm this.
Insert the maintenance tool in the manual
charge socket opening Figure 3-5 and 4-1.
Charge the closing springs by pumping the
handle up and down approximately 38 times
until a crisp metallic "click" is heard. This
indicates that the closing springs are charged
and is shown by the closing spring "charged"
(yellow) indicator. Remove the maintenance
tool. Push the "manual close" button (green).
The circuit breaker will close as shown by the
circuit breaker contacts "closed" (white)
indicator. Push the "manual trip" button (red).
The circuit breaker will trip as shown by the
circuit breaker contacts "open" (black) indicator.
After completing this initial check, leave the
closing springs "discharged" and circuit breaker
contacts "open".
Outdoor storage is NOT recommended. If
unavoidable, the outdoor location must be well
drained and a temporary shelter from the sun,
rain, snow, corrosive fumes, dirt, falling objects
and excessive moisture must be provided.
Container should be arranged to permit free
circulation of air on all sides and temporary
heaters should be used to minimize
condensation. Moisture can cause rusting of
metal parts and deterioration of high voltage
insulation. A heat level of approximately 400
watts for each 4 cubic meters of volume is
recommended with the heaters distributed
uniformly throughout the structure near the floor.
Indoor storage should be in a building with
sufficient heat and air circulation to prevent
condensation. If the building is not heated, the
same general rule for heat as for outdoor
storage should be applied.
Effective 12/98
Page 6 of 47
I.B. 8801C71H01