ALUMAVENT 3965 Series Handbuch für Installation, Betrieb und Wartung - Seite 2

Blättern Sie online oder laden Sie pdf Handbuch für Installation, Betrieb und Wartung für Brand- und Rauchschutzklappen ALUMAVENT 3965 Series herunter. ALUMAVENT 3965 Series 6 Seiten. Control dampers

The goal of a suitable installation is to attach the control damper into the opening in such a
way that damper action is not distorted or disrupted. The checklist below will help you
complete the damper installation in a timely and efficient manner.
1) Review the schedules to see where the dampers should be installed in the building. Inspect the
damper for any signs of damage and dirt.
2) When moving the damper, only use the frame or sleeve. Do not use the blades, linkage, actuators,
or jackshafts to lift the damper as this could cause damage. Use enough support to raise each
section mullion uniformly when handling multi section dampers (see drawing). Avoid excessive
bending, twisting, or racking. The damper must not be dragged or stepped on.
3) Damper blades need to open and/or close properly. It is not recommended to install screws in the
damper frame that interfere with the blade linkage and prohibit this.
4) When putting dampers in ducts or apertures they need to be square and not have any twists.
Squeezing or stretching the damper into the duct or hole is NOT recommended. Dampers that
experience excessive leakage and/or torque needs that exceed damper/actuator design might result
from out of square, racked, twisted, or misaligned installations.
5) Before and after installation, the damper and actuator must be kept clean, dry, and free of debris,
dust, and other foreign materials. Metal shavings, sand, drywall dust, fireproofing materials, plaster,
and paint overspray are all examples of foreign materials.
6) If wall texturing or spray painting will be done within 10 feet (3 metres) of the damper, the damper
should be adequately covered to prevent overspray. Needless dirt and debris on the damper can
result in a higher chance of leakage and/or torque needs that are higher than the damper/actuator
design.
7) In order to maintain, inspect, and service the dampers, appropriate access to dampers and actuators
is needed. It will be required to install a removable section of duct if satisfactory size access cannot
be accomplished.

Electrical Guidelines:

All electrical and or pneumatic connections to damper actuators should be made in accordance with
applicable codes, ordinances and regulations according to region.
Safety Danger
An electrical input may be needed for this
equipment. This work should be performed by
a qualified electrician only.

Pre-Installation Guidelines

Please verify power requirements before
wiring the actuator. Alumavent is not
responsible for any damage to, or failure of the
unit caused by incorrect field wiring. Electrical
and/or pneumatic connections to damper
actuators should be made in accordance with
wiring and piping diagrams developed in
compliance with applicable codes, ordinances
and regulations.

Safety Caution

pg. 2