6. Configuration.
6.1. Lighting connection and control.
The lighting should be connected to terminals 5 and 6. Working time is adjusted by the P1 potentiometer (range from 0 to 180 seconds - 15 seconds
step). When opening and closing the gate lighting is automatically switched on, when gate is not operated lighting can be activated by pressing
STOP button.
NOTE: Automatic control of lighting can be disable by setting potentiometer to „0" position and lighting can be turned on / off using the STOP button..
6.2. Drive connection and control.
The drive should be connected to terminals 7, 8 and 9, where terminal 7 is common to both directions of movement.
P2 potentiometer adjusts working time (range from 6 to 180 seconds - 15 seconds step).
The control unit can be controlled by any DC series transmitter or monostable button connected to terminals 13 and 14 (operates in the sequence
UP - STOP - DOWN - STOP).
6.3. Photocell connection.
NOTE: In accordance with standard EN 12453 governing the safe use of motorised doors, control of the garage door not visible to the user requires the
installation of a photoelectric cell type safety device and/or optical bar.
DIP switch SW1 should be set to ON position.
The photocell must be connected in NC mode (normally shorted) to terminals 10, 11 and 12 (see diagram in section 4.1).
Photocell error is signaled by a flashing red LED under terminal No. 12.
The error may occur in the case of:
1. no connection,
2. photocells damage ,
3. collision.
NOTE: The gate will be disabled if an error occurred
Pin jumper T1
Activation of the safety device during
closing will automatically cause move in
opening direction
6.4. Optical bar connection.
NOTE: In accordance with standard EN 12453 governing the safe use of motorised doors, control of the garage door not visible to the user requires the
installation of a photoelectric cell type safety device and/or optical bar.
DIP switch SW2 should be set to ON position.
The optical bar must be connected to terminals 15, 16 and 17 (see diagram in section 4.1).
Optical bar error is signaled by a flashing red LED under terminal No. 16.
The error may occur in the case of:
1. no connection,
2. optical bar damage
3. collision.
NOTE: The gate will be disabled if an error occurred
4
Pin jumper T2
Activation of the safety device during
opening / closing stops the operation of
the gate.
NOTE: Required setting for rolling grilles control.