AKO AKO-145601 Kurzanleitung - Seite 2

Blättern Sie online oder laden Sie pdf Kurzanleitung für Temperaturregler AKO AKO-145601 herunter. AKO AKO-145601 2 Seiten.

AKO AKO-145601 Kurzanleitung
Adjustment of parameters
Using the programming menu, you will be able to configure the various parameters in order
to adapt the controller's operation to the needs of its installation.
In order to access the programming menu, press the PRG key for 5 seconds, or until the
message ''PwD'' is displayed. Using the N and Q keys enter the password (programmed
into the PSS parameter) and press SET. Once entered correctly, the password will not be
requested again for 30 minutes.
Password
request
5"
ºC
PRG
bar
IN PROGRAMMING
Level 1:
Menus
ºC
bar
Change
menu
ºC
bar
5"
Press the SET button for 5 seconds to exit programming. If no key is pressed for 3
minutes, the controller will exit programming.
SET
*The default value of the password is 5. This may be changed using the PSS parameter.
Table of parameters
The equipment's operation functions are divided into 3 different groups.
The Def. column indicates the default parameters set in the factory. Temperature values are
expressed in ºC. (Equivalent temperature in ºF) and the pressure values in bar (equivalent
pressure in psi).
Description
SH Overheating set point
1. P r
or Initial opening for valve start up
ort Duration of initial start up opening
pro Proportional gain
int Integral time
der Derivative time
Lower overheating alarm
lsM
1: Automatic reset
lSS Lower overheating alarm activation value
LSt Lower overheating alarm turn-on delay time
lsC Lower overheating alarm deactivation time
Maximum pressure alarm in probe 2 0: Deactivated
MpM
1: Automatic reset
Mps Maximum pressure alarm activation value
Mpt Maximum pressure alarm turn-on delay time
MpC Maximum pressure alarm deactivation time
Maximum overheating alarm
HSM
1: Automatic reset
HSS Maximum overheating alarm activation value
HST Maximum overheating alarm turn-on delay time
HSC Maximum overheating alarm deactivation time
Freeze alarm
0: Deactivated
FPM
1: Automatic reset
2: Manual reset
FPS Maximum freeze alarm activation value
FPT Freeze alarm turn-on delay time
FPC Maximum freeze alarm deactivation time
Lower pressure alarm in probe 2 0: Deactivated
LPM
1: Automatic reset
LPS Lower pressure alarm activation value
LPT Lower pressure alarm turn-on delay time
LPC Lower pressure alarm deactivation time
Description
pu Pressure units
0: Bar
2. P r
Tu Temperature units
0: ºC
Selection of expansion valve model connected
1: Danfoss ETS 12.5 / 25B 2: Danfoss ETS 50B
4: Danfoss ETS 250
5: Danfoss ETS 400
EM
7: Alco EX5
8: Alco EX6
10: Alco EX8 (330 s/s) 11: Alco EX8 (500 s/s) 12: Sporlan SEI 0.5~11
13: Sporlan SEI 1.5~20
14: Sporlan SEI 30
16: Sporlan SEI 175
17: Carel E2V
TST Total steps for expansion valve*
DSP Expansion valve speed*
Enter
password*
ºC
ºC
SET
bar
bar
Change value
Accept
changes
Level 2:
Level 3:
Parameters
Values
ºC
ºC
bar
bar
Change
Change
SET
Accept
parameter
value
changes
ºC
ºC
SET
bar
bar
PRG
GROUP 1
Values Min.
(K)
3.5
(%)
0
(Sec.)
0
0.1
(Sec.)
0
(Sec.)
0
0: Deactivated
0
2: Manual reset
(K)
0.5
(Sec.)
1
(K)
1
0
2: Manual reset
(bar/psi) -999
(Min.)
1
(bar/psi) -999
0: Deactivated
0
2: Manual reset
(K)
10.0
(Min.)
1
(K)
7.0
0
(ºC/ºF)
-100
(Sec.)
5
(ºC/ºF)
-100
0
2: Manual reset
(bar/psi) -999
(Sec.)
5
(bar/psi)
0
GROUP 2
Values Min.
1: Psi
0
1: ºF
0
3: Danfoss ETS 100B
6: Alco EX4
1
9: Alco EX7
15: Sporlan SEI 100
0
0
Description
pss Parameter access password
3. P r
Type of refrigerant gas used:
3: R-407C
rft
8: R-HFO1234ze 9: R-744 10: R-407A 11: R-407F 12: R-507A
13: R-245F
PSH Pressure probe range (Maximum)
PSL Pressure probe range (Lower)
PSO Pressure probe calibration (S2)
TSO Pressure probe calibration (S1)
JCR Expansion valve opening speed limit
UrL Maximum expansion valve opening limit
LrL Lower expansion valve opening limit
Ft Reading delay for probes (S1 and S2)
COR Lower expansion valve forced opening value
Display mode:
DM
CID Communication direction
CSP Communication speed
INI Initial settings (enter password and press SET)
* The TST and DSP parameters are adjusted automatically when the expansion valve model
is selected. They should only be changed by qualified staff. AKO is not responsible for any
damage that may be inflicted on the installation.
Messages
PS
Problem in the pressure sensor
TSD Probe 1 not connected
TsC Crossed temperature probe
MOP Maximum Operation Pressure (MOP) alarm
LOP Lower Operation Pressure (LOP) alarm
HS
Maximum overheating alarm
LS
Lower overheating alarm
FRA Frost detection alarm
Def. Max.
STP Regulation stopped by external thermostat (ON/OFF Input)
10
30
50
100
CAL Expansion valve initialisation
5
300
Valve closing underway due to fault in the electricity supply (emergency power
CLE
3
99.9
supply required)
120
999
IMPORTANT: In the event of an alarm or fault in any of the probes, the
30
999
controller closes the liquid solenoid and expansion valve until the problem is
1
2
solved.
3
30
15
300
3
30.5
1
2
9
999
1
15
8
999
0
2
AKO-D141xx
30
40.0
3
600
27
37.0

Technical specifications

0
2
0
200
Power supply .......................................................................24 V~ +10% / -15%, 50/60 Hz
Working ambient temperature ................................................-10 to 50 ºC, moisture <90 %
30
200
Storage ambient temperature .................................................-20 to 60 ºC, moisture <90 %
3
200
Relay solenoid valve ........................................................ (EN60730-1: 2(2) A 250 V~ SPST)
0
2
No. of relay operations..........................................................EN60730-1: 100.000 operations
Maximum voltage in the SELV circuits............................................................................20 V
0
999
Protection degree ...........................................................................................................IP2X
5
200
Connections ..................................Terminal to screw for cables with a section of up to 2.5 mm
0.3
999
Control device classification: Built-in assembly, with Type 1.B automatic operation action feature,
for use in clean situations, logical support (Software) class A and continuous operation. Degree of
Def. Max.
contamination 2 acc. to UNE-EN 60730-1.
0
1
Double power input insulation, secondary circuit and relay output.
0
1
Rated pulse voltage ...................................................................................................2500 V
Pressure ball test temperature
Voltage and current declared by the EMC tests ........................................................207 V, 17 mA
1
17
Radio interference suppression test current ....................................................................270 mA
For further information, refer to the user manual available on our
262
999
website: www.ako.com
250
999
GROUP 3
0: R-22
1: R-134A
4: R-410A 5: R-717
6: R-23
0: Displays options 1 to 4 sequentially
1: Overheating value (ºK)
2: Suction pressure value (Probe 2)
3: Valve opening (%)
4: Temperature value (Probe 1)
5: Overheating set point
Description
EXPANSION
LIQUID
VALVE
SOLENOID
AKO-145601
EVAPORADOR
SET
Accessible parts..........................................................75 ºC
Parts that position active elements.............................125 ºC
Values Min.
Def. Max.
0
5
999
2: R-404A
7: R-507C
0
1
13
(bar/psi) -999
15
999
(bar/psi) -999
-1
999
(bar/psi) -19.9
0
19.9
(ºC)
-19.9
0
19.9
(%)
0.1
OFF
99.9
(%)
0
100
100
(%)
0
0
100
(Sec.)
0.1
1
10.0
(%)
0.0
OFF
100
0
1
5
1
1
128
(BPSx100) 48
96
384
0
0
999
ºC
%
bar
PRG
SET
S1
S2
2