AKO AKO-15450 Handbuch - Seite 2

Blättern Sie online oder laden Sie pdf Handbuch für Controller AKO AKO-15450 herunter. AKO AKO-15450 2 Seiten. Pid controller

Alarm 1 Operation
tAL1=1 (Min)
tAL1=0 (Max.)
ON
AL1
AL1
OFF
Si ACo1 = 0
ALt1
ALt1+Adi1
AHt1+Adi1
AHt21
Si ACo1 = 1
SP1+ALt1
SP1+ALt1+Adi1
SP1+AHt1+Adi1
SP1+AHt1
Si ACo1 = 2
SP2+ALt1
SP2+ALt1+Adi1
SP2+AHt1+Adi1
SP2+AHt1
Start
Stop
Stop
Start
ACo1 is the alarm 1 configuration parameter
5- Accessories
PARAMETERS TRANSFER
AKO-14918 portable server, with no power supply, in which
parameters programmed in a powered controller can be copied by
transfer. Parameters can be transferred again from the server to
other identical powered controllers.
6- Maintenance and Warnings
Clean the controller surface with a soft cloth and soap and water.
Do not use abrasive detergents, petrol, alcohol or solvents.
The use of the unit without observing the manufacturer's
instructions may alter its safety qualification. To ensure correct
operation of the apparatus, only probes supplied by AKO should be
used.
7- Parameters and messages
Values in the Def. column are factory-set.
Level 1
Menus and Description
SPCF
Level 2
Set Point parameters
Level 3
Description
Set point lower limit
LL1
(It cannot be set below this value)
Set point upper limit
HL1
(It cannot be set above this value)
CAn
Sensor calibration (Offset)
Set Point 2 lower limit
LL2
(It cannot be set below this value) (only CONTROL 2 CIo=1, 2, 3)
Set Point 2 upper limit
HL2
(It cannot be set above this value) (only CONTROL 2 CIo=1, 2, 3)
CFG
Level 2
Configuration Parameters
Level 3
Description
Sensor type selection
PbS
(0=Pt100) (1=TcJ) (2=TcK) (3=4-20mA)
HES
Maximum scale value for the sensor type in mA (Only if PbS=3)
LES
Minimum scale value for sensor type in mA (Only if PbS=3)
Blocking the scale between HES and LES (Only if PbS=3)
bES
(0=Free scale) (1=Blocked scale)
Type of control: (0=PID for CONTROL 1) (1=ON/OFF for CONTROL 1)
rEG
(CONTROL 2 always ON/OFF, only if Clo=1,2,3)
Type of operation in CONTROL 1
HC1
(0=Direct, cold)(1= Reverse, heat)
Type of operation in CONTROL 2
HC2
(0=Direct, cold)(1= Reverse, heat) (Only if Clo=1,2,3)
CONTROL 1, CONTROL 2 Ratio Type (Only if CONTROL 2 CIo=1, 2, 3)
o2C
(0 = Two independent stages) (1 = Two related stages) (2 = Neutral Zone)
Temperature display mode: (0 = Integers in ºC) (1 = One decimal in ºC)
rES
(2 = Integers in ºF) (3 = One decimal in ºF) (4 = Integers in mA) (5 = One decimal in mA)
CONTROL 1 status with faulty sensor:
Er1
(0=OFF) (1=ON)
CONTROL 1 status with faulty sensor: (Only if Clo=1,2,3)
Er2
(0=OFF) (1=ON)
Enable / Disable CT alarm
CtEn
(0=Disabled) (1=Enabled)
4-20 mA
converter
AnCF
Level 2
(only if CIo=0, 1, 2) and 4-20 mA / 0-10 V module
Level 3
Description
Maximum output value scale for 20 mA / 10 V
AHES
(If PbS=0,1,2,) (If PbS=3, AHES=HES)
Minimum output value scale for 4 mA / 0 V
AHES
(If PbS=0,1,2,) (If PbS=3, ALES=HLS)
onoF
Level 2
ON/OFF Configuration Parameters (only if rEG=1) or (Clo=1,2,3)
Level 3
Description
diF1
CONTROL 1 Differential (Hysteresis) (only if rEG=1)
CONTROL 2 Differential (Hysteresis) (only CONTROL 2 CIo=1, 2, 3)
diF2
ton1
Minimum CONTROL 1 time in ON (only if rEG=1)
ton2
Minimum CONTROL 2 time in ON (only CONTROL 2 CIo=1, 2, 3)
toF1
Minimum CONTROL 1 time in OFF (only if rEG=1)
Minimum CONTROL 2 time in OFF (only CONTROL 2 CIo=1, 2, 3)
toF2
inPt
Level 2
Digital INPUT/OUTPUT (I/O, 5-, 6+) and Relays R1, R2, R3 configuration
Level 3
Description
Digital Input / Output and R1, R2, R3 relays
(0= Digital Output SSR CONTROL 1, R1=ALARM 2, R2=ALARM 1) *
(1= Digital Output SSR CONTROL 1, R1=CONTROL 2, R2=ALARM 1) *
(2= Digital Input, R1=ALARM 1, R2=CONTROL 1, R3= CONTROL 2) *
Clo
(3=Digital Input, MODULE 4-20 mA / 0-10 V CONTROL 1,
R1=CONTROL 2, R2=ALARM 1) (only with MODULE 4-20 mA / 0-10 V)
(4=Digital Input, MODULE 4-20 mA / 0-10 V CONTROL 1,
R1=ALARM 2, R2=ALARM 1) (only with MODULE 4-20 mA / 0-10 V)
Digital input configuration if Clo=2,3,4
Cdln
(0=External alarm) (1=Variation in Set point) (2=Start-Stop)
Digital input status inversion:
IPo
(0=Closed contact) (1=Open contact)
Av. Roquetes, 30-38 | 08812 Sant Pere de Ribes | Barcelona | España
Tel. (34) 938 142 700 | Fax (34) 938 934 054 | e-mail: [email protected] |
Apartado (P.O. Box), 5 | 08800 Vilanova i la Geltrú | Barcelona | España
Alarm 2 Operation
tAL2=1 (Min)
tAL2=0 (Max.)
AL2
AL2
VALUE
Si ACo2 = 0
ALt2
ALt2+Adi2
AHt2+Adi2
Si ACo2 = 1
SP1+ALt2
SP1+ALt2+Adi2
SP1+AHt2+Adi2
Si ACo2 = 2
SP2+ALt2
SP2+ALt2+Adi2
SP2+AHt2+Adi2
Start
Stop
Stop
ACo2 is the alarm 2 configuration parameter
Transfer
Power supply
Programming
Values
Min. Def. Max.
(ºC/ºF/mA)
-99,9
(ºC/ºF/mA)
LL1
(ºC/ºF/mA) -20,0
(ºC/ºF/mA)
-99,9
(ºC/ºF/mA)
LL2
Values
Min. Def. Max.
0
-99,9
-99,9
0
0
0
0
0
0
0
0
0
or
repeater c
onfiguration parameters
Values
Min. Def. Max.
-99,9
-99,9
Values
Min.
(ºC/ºF/mA)
-50,0
(ºC/ºF/mA)
-50,0
(sec.)
0
(sec.)
0
(sec.)
0
(sec.)
0
Values
Min.
0
0
0
IdY
Digital input enabling delay
USI1
Set point SP 1 variation if CdIn=1
Pld
Level 2
Level 3
GAin
Gain (see item 4.1)
ti
Overall time (see item 4.1)
AHt2
VALUE
td
Derivative time (see item 4.1)
SP1+AHt2
toUt
Cycle Control time
SP2+AHt2
Start
AT key blocking
AtEn
(0=Yes, blocked) (1=No, unblocked)
ALr1
Level 2
Level 3
AKO-14918
Alarm 1 type
tAL1
(0=Max) (1=Min) (2=Max+Min)
AHt1
Max for Alarm 1
ALt1
Min for Alarm 1
Alarm 1 configuration (0=Absolute)
ACo1
(1=Relative to set point SP1) (2=Relative to set point SP2)
Adl1
Alarm 1 differential
AdE1
Alarm 1 delay from the moment at which it should enabled
Ado1
Alarm 1 delay at start-up
Optional cancellation of output alarms by pressing once a key.
AtA
(0=Allows to cancel the output alarms) (1=Not allows to cancel the output alarms)
ALr2
Level 2
Level 3
Alarm 2 type
tAL2
(0=Max) (1=Min) (2=Max+Min)
AHt2
Max for Alarm 2
ALt2
Min for Alarm 2
Alarm 2 configuration (0=Absolute)
ACo2
(1=Relative to set point SP1) (2=Relative to set point SP2)
Adl2
Alarm 2 differential
AdE2
Alarm 2 delay from the moment at which it should enabled
Ado2
Alarm 2 delay at start-up
PAr
Level 2
-99,9
HL1
Level 3
Initial parameters
999,9
2500
PdE
(1=YES, configure to "Def" and exit programming)
0,0
20,0
Parameters transfer
Ptr
(0=Disabled) (1=Send) (2=Receive)
-99,9
HL2
PAS1
Password to parameters and information
CAd
Address for units with communication
999,9
2500
Ct
Level 2
Level 3
CtHA
Max for Alarm CT
CtLA
Min for Alarm CT
0
3
Ctdy
Alarm CT delay from the moment at which it should enabled
100,0
2500
CtUA
Current load value (display)
0
2500
Ctin
Primary current value CT transformer
Ctou
Secondary current value CT transformer (0=0,05A)
0
1
Output CONTROL 1 status in case of CT alarm:
CtEr
(0=OFF) (1=No change)
0
1
CT alarm memory
CtLC
(0=Without memory) (1=With memory)
1
1
MESSAGES
AH1
Flashing with temperature - Sensor temperature exceeds the parameter programmed in AHt1
1
1
AH2
Flashing with temperature - Sensor temperature exceeds the parameter programmed in AHt2
AL1
Flashing with temperature - Sensor temperature is lower than the parameter programmed in ALt1
0
2
AL2
Flashing with temperature - Sensor temperature is lower than the parameter programmed in ALt2
EAL
Flashing with temperature - Active digital input
1
5
StoP
Stopped controller if CdIn=2 and digital input enabled
E1
Sensor failure (Open circuit, crossed, temperature out of range)
0
1
EE
EEPROM memory failure
rA
RAM memory failure
0
1
PAS
Password request to enter programming parameters
Flashing with temperature - The load intensity circulating through the CT current transformer exceeds
ACt
1
1
the programmed parameter in CtHA or is lower than the programmed parameter in CtLA
----
Incorrect resolution - See rES parameter
* In the 4-20 mA / 0-10 V module, it only acts as a repeater/converter.
200,0
2500
8- Technical data
-50,0
2500
Range according to type of sensor configured:
Pt 100.............................................................................-99,9 ºC to 850,0 ºC (-148 ºF to 1562 ºF)
Def.
Max.
J Thermocouple.................................................................-99,9 ºC to 800,0 ºC (-148 ºF to 1472 ºF)
1,0
50,0
K Thermocouple.................................................................-99,9 ºC to 1370 ºC (-148 ºF to 2498 ºF)
1,0
50,0
4-20 mA.......................................................................................4 mA = 0% to 20 mA = 100%
0
250
Set Point 1 range...................................................................................................-99.9 to 2500
0
250
Set Point 2 range...................................................................................................-99.9 to 2500
0
250
Resolution, Set Point and differential ........................................0,1 or 1 configurable by parameter rES
0
250
Accuracy ...........................................................................±0,25 % (Pt100, TcJ, TcK); ±1,5% (mA)
Def.
Max.
R1/OUT relay: CONTROL 2 or ALARM 1 or 2 (configurable by param. CIo) .....SPST-NO, 6A, 250V, cosj
R2/AL relay: CONTROL 1 or ALARM 1 (configurable by param. CIo)...................SPDT, 5A, 250V, cosj
R3 relay: CONTROL 2 (with Relay 3 module) (configurable by param. CIo) ..........SPDT, 5A, 250V, cosj
Maximum input power .......................................................................................................3 VA
0
4
Working ambient temperature.................................................................................. 0 ºC to 55 ºC
Storage ambient temperature ................................................................................-30 ºC to 70 ºC
Installation category .........................................................................II under EN 61010-1 standard
Pollution degree ..............................................................................II under EN 61010-1 standard
0
2
Double insulation between the power supply, the secondary circuit and the relay output.
0
1
AKO ELECTROMECÀNICA, S.A.L.
www.ako.com
We reserve the right to supply materials that might vary slightly to those described in our
Technical Sheets. Updated information is available on our website: www.ako.com
PID Parameters (only if rEG=0)
Description
Alarm 1 Parameters
Description
Alarm 2 Parameters (If Clo=0, 4, R1=Alarm 2)
Description
General Parameters
Description
CT Current transformer parameters (If CtEn=1 in CT module)
Description
(sec.)
0
0
250
(ºC/ºF/mA)
-99,9
0,0
2500
Values
Min.
Def.
Max.
(%)
0
50
100
(sec.)
0
100
999
(sec.)
25
0
999
(sec.)
1,0
2,0
100,0
0
0
1
Values
Min.
Def.
Max.
0
0
2
(ºC/ºF/mA)
-99,9
999,9
2500
(ºC/ºF/mA)
-99,9
-99,9
2500
0
0
2
(ºC/ºF/mA)
1,0
1,0
20,0
(min.)
0
0
250
(min.)
0
0
250
0
0
1
Values
Min.
Def.
Max.
0
0
2
(ºC/ºF/mA)
-99,9
999,9
2500
(ºC/ºF/mA)
-99,9
-99,9
2500
0
0
2
(ºC/ºF/mA)
1,0
1,0
20,0
(min.)
0
0
250
(min.)
0
0
250
Values
Min.
Def.
Max.
0
0
1
0
0
2
0
2
999
0
0
254
Values
Min.
Def.
Max.
(A)
100,0
0,0
100,0
(A)
0,0
0,0
100,0
(min.)
0
0
250
(A)
0,0
Value
100,0
(A)
0
25
999
(A)
0
0
999
0
1
1
0
1
1
=1
=1
=1