Cynergy3 IWR-5 Betriebshandbuch - Seite 4
Blättern Sie online oder laden Sie pdf Betriebshandbuch für Empfänger Cynergy3 IWR-5 herunter. Cynergy3 IWR-5 8 Seiten. Five channel industrial wireless pressure/temperature receiver
IWR-5 Wireless Pressure & Temperature Receiver - Operating Manual
Dipswitch Configuration
The 8 way Dipswitch 1 is used to configure the basic functionality of the IWR-5
The RF network code must be the same as the IWPT units to be used with the receiver
unit.
Switches 1, 2, 3 & 4 select the network code as below
Switch 5 and 6 select the number of transmissions which are missed before the Alarm
relay output switches to the alarm condition.
Switch 7 and 8 Configure the action of the Alarm Relay output. This can also be
configured to exact alarm values using the USB port and the IWR-Set software.
Relay 1 switches OFF any I/P above 50%
Relay 1 switches OFF any I/P above 75%
Relay 1 switches OFF any I/P above 25%
Relay 1 Configured via USB & IWR-Set software
RF NETWORK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Missed Transmissions
4
2
6
No Alarm
Relay Action
Page 4
1 2 3 4
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
5 6
0 0
0 1
1 0
1 1
7 8
0 0
0 1
1 0
1 1
IWR-5 Iss2.1