DOLD VARIMETER IMD RN 5897/300 Technik der Überwachung - Seite 2
Blättern Sie online oder laden Sie pdf Technik der Überwachung für Messgeräte DOLD VARIMETER IMD RN 5897/300 herunter. DOLD VARIMETER IMD RN 5897/300 8 Seiten. Insulation monitor
Function
The device is supplied with DC auxiliary voltage via terminals A1(+) / A2.
Switching on the auxiliary voltage (Power-On) is followed by an internal
self-test for 12 sec (see „Device test functions"). The test process is visible
in the status LED. After this, measurement of the insulation resistance
in the measuring circuits begins and the the colour of the status LED
changes to green.
Measuring circuit
(Insulation measurement between terminals L(+) / L(-) and PE1/PE2)
The terminals L(+) and L(-) are connected directly to the voltage system
to be monitored. A broken wire detection creates a fault signal if there is
no low-ohmic connection between both terminals.
The type of network (AC, DC, 3NAC) has to be selected.
Also the terminals PE1 and PE2 have to be connected with 2 separate
wires to the protective earth. An interruption of a wire also causes a fault
signal (see section "Behavior on faulty connection"). The monitoring of
the PE connection cannot be de-activated.
To measure the insulation resistance an active measuring voltage with
changing polarity is connected between L(+)/L(-) and PE1/PE2.
At the end of a measuring cycle the actual insulation resistance is produced
and indicated. The relays for alarm K1 and pre-alarm K2 switch when
dropping under the adjusted response values. In addition the LED changes
to orange color on pre-alarm or to red color on alarm.
Manual reset of fault message
The rotary switch "UN" is devided in 2 sections. So additional to the type of
voltage system also manual or autoreset can be selected. (Alarm storing:
manual reset, no alarm storing: auto reset).
If manual reset is activated the insulation fault signals of the measuring
circuit are stored when dropping under the adjusted response values
also if the insulation resistance goes back to healthy state. Pressing the
„Reset" button on the front side for 2 s, the alarm signal are reset if the
actual insulation resistance is in healthy state.
Indicator relay for insulation fault signal
For the indicator relays K1 (contacts 11-12-14, for alarm) and K2 (contacts
21-22-24, for pre-alarm) the function energized on trip or de-energized on
trip can be set via pre-alarm rotational switch "R
resistance drops below the adjusted response value.
Broken wire detection
As described in section "Measuring circut", the measuring circuits L(+)/L(-)
and the protective conductors PE1/PE2 are constantly monitored for wire
breaks – not only at Power-On or a manual or occasional automatic test. The
response time of monitoring is only a few seconds. Broken wire detection
between L(+) and L(-) is performed via coupled alternating voltage. This
alternating voltage is short-circuited if the terminals are connected to the
connected mains at low-resistance. The device detects that the mains to
be monitored is properly connected.
Since this broken wire detection is carried out with alternating voltage, large
capacitances should be avoided between L(+) and L(-), since the capacitive
reactance of these capacitances also short-circuits this alternating voltage.
The device would no longer detect a connection fault on L(+)/L(-).
Especially parallel lines should be avoided over larger distances.
If larger capacitances between L(+)/L(-) cannot be avoided or if the coupled
alternating voltage interferes with the system, the broken wire detection
can be de-activated using alarm rotary switch "R
or continuous monitoring (every 2 minutes for 10 sec) are the possible
options. If the broken wire detection on L(+)/L(-) is de-activated no AC
voltage is injected.
The broken wire detection on PE1/PE2 cannot be de-activated.
Device test functions
Principally, 2 different test functions are implemented: The "self-test" and
the "expanded test":
The self-test of the device is performed automatically after Power-On and
every full operating hours. It can also be triggered manually at any time by
pressing the "Test" button at the device front for 2 sec.
With the self-test, contrary to the expanded test, the status of the Indicator
relays is not affected; the sequence is as follows:
The self-test is indicated via LED with orange flash code 1. For approx.
5 s to negative test phase. Within these 5 s the internal measuring circuit
is checked for failures. Then the measuring pulse is switched for approx.
5 s to positive test phase and more internal tests take place. If no failures
turned up and had been recognized, the measurement continuous. The
extended test procedure is started when during or at the end of the above
described self-test (12 s) the test button is pressed again for 2 s.
The sequence is similar to the self-test (2 measuring phases of 5 s each)
but in addition the output relays go in alarm stated. The LED shows
orange flash code 2. The test phases of the extended test will be repeated
continuously. The extended test can be finished after the first complete
sequence (approx. 10 sec) by pressing the "reset" button for 2 seconds.
The device starts the insulation monitoring again.
Measuring voltage
Relay state K1 and K2
Test signal: Button Test > 2 s or X1/X2 < 3 s
1)
Reset signal: Button Reset > 2 s or X1/X2 > 3 s
2)
To initiate the extended test (Test 2) the test signal must be operated
3)
" when the insulation
within the self test (Test 1) again.
pA
The reset signal has here no function, as the first complete sequence
4)
of extended test (Test 2) is not finished.
". Monitoring deactivated
A
2
U
Self test (Test 1)
Insulation
Insulation
measurement
measurement
Duration: approx. 12s
Positive
Negative
1)
Test signal
2)
Reset signal
Alarm
No Alarm
Self test (Test 1)
Continuous extended
Insulation
Duration: approx. 12s
test (Test 2)
measurement
Duration: approx. 10s
3)
4)
M12462
10.11.23 en / 800A
t