DOLD MINISTART GF 9016 Handbuch
Blättern Sie online oder laden Sie pdf Handbuch für Industrielle Ausrüstung DOLD MINISTART GF 9016 herunter. DOLD MINISTART GF 9016 4 Seiten. Softstarter and softstop device
Power Electronics
MINISTART
Softstarter And Softstop Device
GF 9016
Product Description
The softstarter and softstop device GF 9016 is a electronic control unit for
the smooth starting and stopping of three-phase asynchronous machines.
The GF 9016 slowly ramps up the current on two phases, therefore
allowing the motor torque to build up slowly. This reduces the mechanical
stress on the machine and prevents damage to conveyed material.
When the motor is up to full speed the power semiconductors in GF 9016
are bridged to prevent internal power losses and heat build up. In addition
GF 9016 allows a softstop function prolonging the stop time of the motor,
preventing high counter torques from abruptly stopping the motor.
Block Diagram
1L1
3L2
5L3
Supply
votlage
Electronic
Trigger pulse
generator
Control
bridging
2T1
4T2
6T3
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
M9816_a
t
t
Ramp control
U start
for
Translation
of the original instructions
Your Advantage
• For soft and shockfree start of your asynchronous motors
• Less wearing and longer life for your motors and components
• Space saving and easy fitting
• Reduce load from supply mains by reducing of starting current
Features
• According to IEC/EN 60947-4-2
• Softstart with softstop
• For motors up to 22 kW
• 2-phase control
• Adjustable start up and deceleration time als well as starting voltage,
optionally with kickstart
• Without auxiliary voltage
• W3 connection is possible
• Up to 15 kW: Width 45 mm
Up to 22 kW: Width 52.5 mm
Approvals and Markings
Applications
• Motors with gear, belt or chain drive
• Fans, pumps, conveyor systems, compresseors
• Packaging machines, door drives
• Start current limiting on 3 phase motors
Connection Terminals
Terminal designation
L1, L2, L3
X4
T1, T2, T3
X1+
X1
Start
X2
X1
X2
Boost
X3
X3
X4
X5, X6
X5
Interference
X7, X8
X6
X7
Bypass
X8
1
Signal description
Phase voltage L1, L2, L3
Motor voltage U, V, W
Output + 24V
Input + 24 V
at variant with wide voltage
Start / Stop
Kickstart 0,5 s
0 V
Indicator output, fault
Indicator output, device bridged