Egcon MP3 Benutzerhandbuch - Seite 8
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Kontrolleinheit Egcon MP3 herunter. Egcon MP3 9 Seiten. Acu (ats control unit)
ACU-MP3 Manual
9.4. UVR contacts(ST1, ST2) of commercial power gets CLOSE.
9.5. Generator power lamp turns on when generator power is applied.
9.6. If generator power is normal, ATS is transferred to generator power's side after set time
delay and insertion lamp of generator power turns on.
9.7. If commercial power is applied, lamp of commercial power turns on and after set time
delay, ATS is transferred and insertion lamp of commercial power turns on.
9.8. UVR contacts(ST1, ST2) of commercial power is OPEN.
10. TEST Operation Test
10.1. TEST mode is available during both AUTO and MANU mode.
10.2. While commercial power is normal and ATS is transferred to commercial power, if MODE
switch is pressed over 10 sec, TEST LAMP turns on.
10.3. If TEST mode is set, UVR contacts(ST1, ST2) of commercial power are CLOSE.
10.4. If generator power is not applied within 10 sec, mode is changed to precious mode after
buzzer alarms.
10.5. Lamp of generator power turns on when generator power is applied, and ATS is
transferred to generator power's side after time delay.
10.6. When ATS is normally transferred to generator power, ATS will be transferred to
commercial power after time delay for transferring to commercial power.
10.7. Insertion lamp of commercial power turns on.
10.8. TEST mode terminates and mode changes to precious mode.
11. Problem Causes and Solutions
Symptom
Indication lamps turn on
when ATS is transferred to
the reverse and ATS is
not transferred when
transfer button is pressed.
Lamp of commercial
power flickers.
Buzzer keeps alarming
and transfer indication
lamp flickers.
Cause
Assistant contact of ATS is
reversely connected.
One of the three phases of
commercial power is absent
or there is a phase that is
not connected.
Contact of ATS is not
completely transferred even
after controller's trial to
transfer
Assistant contact of ATS is
not connected correctly
EGCON CO., LTD
Solution
Correct wiring according to circuit
diagram.
Check whether the voltage of each phase
is normal and there is absent wiring.
Transfer ATS mechanically using lever
after blocking power supply to the
controller and then connect power to the
controller.
Correct wiring according to circuit
diagram.