3. User & Operating Instructions.
3.1
To Start the Heater
1. Ensure gas supply is turned on.
2. Electrical supply to the controls is on.
3. Ensure that the controls are correctly set
i.e.;
Clock is correctly set.
Heater program is correctly set.
Required room temp is correctly set
4. Once the heating controller 'calls for heat'
power will be supplied to the heater(s). The
red neon will then illuminate.
5. After a pre-purge period of 10 seconds the
burner will ignite and the amber neon will
then illuminate.
6. If lockout occurs press the lockout reset
button (if available), or switch off electrical
supply and restart after 15 seconds.
7. If lockout occurs three times consecutively
switch off and isolate the gas and electric-
ity supplies.
Call an AmbiRad Service Engineer.
3.2.
To Switch Off Heater
1. Switch off electrical supply to the heater.
The burner will stop and the fan will shut
off.
2. If the heater is to be switched off for
periods in excess of one week it is highly
recommended that both the gas and the
electrical supplies are turned off.
AmbiRad Limited Fens Pool Avenue
Brierley Hill West Midlands DY5 1QA
United Kingdom
Telephone 01384 489700
Facsimile 01384 489707
Email
Website
Technical Support
www.ambirad.co.uk
www.s-i-d.co.uk
3.3.
Routine Maintenance between Service
Intervals
After ensuring that the heater is cold and
mains electric isolated, cleaning of the
reflectors with a soft cloth and a mild
detergent (non solvent based cleaners only)
in water can be undertaken.
Additional removal of dust from the radiant
tubes, burner and heat exchanger can be
undertaken.
3.4
Frequency of Servicing
The manufacturer recommends that to
ensure
continued
operation
of
recommended that the heater is serviced
annually by a competent person e.g. every
year in normal working conditions but in
exceptional dusty or polluted conditions
more frequent servicing may be required.
The manufacturer offers a maintenance
service.
Details are available on request.
For Service requirements, please contact
AmbiRad
For further technical and service support
visit our Support Information Database at
www.s-i-d.co.uk
AmbiRad is a registered trademark of AmbiRad Limited. Because of continuous product
8
innovation, AmbiRad reserve the right to change product specification without due notice
efficient
and
safe
the
appliance
it
is