Ambirad AR22/32' SL Manual de instalación y mantenimiento - Página 4
Navegue en línea o descargue pdf Manual de instalación y mantenimiento para Calentador de gas Ambirad AR22/32' SL. Ambirad AR22/32' SL 20 páginas. Gas fired radiant tube heaters
- 1. Table of Contents
- 2. AR and ARE Series Gas Fired
- 3. Gas Connection
- 4. Standards
- 5. Assembly Instructions
- 6. Fitting Reflectors and End Caps
- 7. Burner/Fan/Damper Assembly
- 8. AR and ARE Series Double Linear
- 9. HB and DL Damper Settings
- 9. Installation – Suggested Methods
- 9. Of Heater Suspension
- 10. Flue Connection
- 11. Commissioning for Individually
- 12. Routine Service
- 13. Trouble Shooting Checklist
- 14. User Instructions for Ambi-Rad
Figure 1 Correct installation of flexible gas connection
4
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 11984 Class 1 Type C Construction
1 Metre Long - Ambi~Rad Part No. 6500-2
COLD POSITION
Valve
NOTE:
Elbows must be fitted to eliminate
50 ± 2 0 mm
sharp bends near end fittings.
± 5 mm
Valve
Union end
Corrugated Flexible Metallic Hose Assemblies to BS 6501 Part 11984 Class 1 Type C Construction
600 mm Long - Ambi~Rad Part No. 6500
COLD POSITION
Valve
NOTE:
Elbows must be fitted to eliminate
50 ± 2 0 mm
sharp bends near end fittings.
± 5 mm
Valve
X X
Union end
COLD POSITION
X X
COLD POSITION
HOT POSITION
*NOTE*
*NOTE* - CORRECT INSTALLATION AS SHOWN WILL ALLOW
FOR APPROX. 150 mm OF MOVEMENT DUE TO EXPANSION.
THIS INSTALLATION LAYOUT IS THE ONLY METHOD RECOMMENDED
BY THE INSTITUTE OF GAS ENGINEERS,THE MANUFACTURER AND
AMBI-RAD LTD
N.B. BURNER ILLUSTRATED IS AR SERIES, BUT INSTRUCTIONS
ARE EQUALLY APPLICABLE TO ALL OTHER RANGES OF BURNERS.
NOTE:THESE INSTRUCTIONS MUST BE CARRIED OUT IN
ACCORDANCE WITH THE RELEVANT PROVISIONS OF THE
GAS SAFETY (INSTALLATIONS AND USE) REGULATIONS 1984
(AS AMENDED) AND THE MANUFACTURERS RECOMMENDATIONS.
HOT POSITION
*NOTE*
X X
*NOTE* - CORRECT INSTALLATION AS SHOWN WILL ALLOW
FOR APPROX. 100 mm OF MOVEMENT DUE TO EXPANSION.
THIS INSTALLATION LAYOUT IS THE ONLY METHOD RECOMMENDED
BY THE INSTITUTE OF GAS ENGINEERS,THE MANUFACTURER AND
AMBI-RAD LTD
N.B. BURNER ILLUSTRATED IS AR SERIES, BUT INSTRUCTIONS
ARE EQUALLY APPLICABLE TO ALL OTHER RANGES OF BURNERS.
NOTE:THESE INSTRUCTIONS MUST BE CARRIED OUT IN
ACCORDANCE WITH THE RELEVANT PROVISIONS OF THE
GAS SAFETY (INSTALLATIONS AND USE) REGULATIONS 1984
(AS AMENDED) AND THE MANUFACTURERS RECOMMENDATIONS.
COLD POSITION
X X
Greater than 5 mm