10 User Level Dialog
(xxxx = 125% v. f. s.)
Dialog
Value
Description
item
MENU
-1... 9999
Primary display, e.g. the value selected in the DISP menu
DISP
-----
Display value which should be permanently in the display:
act
actually measured value
sp1
switching point SP1
SP2
switching point SP2
max
maximum peak value
min
minimum peak value
ACT.
-1... 9999
Display of actually measured value in bar
UNIT
Fixing the unit
(only
(The unit is shown in the display appr. every 30 sec for appr. 5 sec)
V 7.X)
bar
bar
psi
psi x
psi
psi
hPa
hPa
mbar
mbar
NOTE: no choice of the unit possible at UTS 7. Only °C possible!
SP.1
-----
none
switching output SP1 deactivated
wind
window technology
stnd
standard evaluation SP1
erro
error output
ON-1
-1... xxxx
Switch-on point for SP1;
NOTE: if the ON-value is set smaller than the OFF-value you receive a decreasing
switch point evaluation.
OFF-1
-1... xxxx
Switch-off point for SP1
DLY1
0.0... 9.9 s
Switch-on / switch-off delay for SP2 in seconds
INV-1
-----
Inversion of switching output SP1
hlfs
high-level-fail-save (normally open function)
Ilfs
low-level-fail-save (normally closed function)
SP.2
-----
none
Switching output deactivated
wind
window technology
stnd
standard evaluation SP2
erro
error output
10
= bar
= psi x 10
= psi
= Hekto-Pascal
= millibar
Dialog
Value
Description (continued)
item
ON-2
-1... xxxx
Switch-on point for SP2
NOTE: if the ON-value is set smaller than the OFF-value you receive a
decreasing switch point evaluation.
OFF-2
-1... xxxx
Switch-off point for SP2
DLY2
0.0... 9.9 s
Switch-on / switch-off delay for SP2 in seconds
INV-2
-----
Inversion of switching output SP2
hlfs
high-level-fail-save (normally open function)
llfs
low-level-fail-save (normally closed function)
MAX -1
... xxxx
Display of the peak value "max"
CLRH
-----
Delete the maximum value memory
-----
no deletion
clr
delete value
CDLY
0.0... 9.9 s
Time setting to delete the maximum value memory after switching
point SP1 is reached (manual deletion is still possible)
MIN
-1... xxxx
Display of the peak value "min"
CLRL
-----
Delete the minimum value memory
-----
no deletion
clr
delete value
OFFS
-9.9... +xx
Measured value offset in bar
CUT
0.0... +xx
Cut-off i.e. signal suppression at measuring range start in bar
DLDS
0.0... 9.9 s
Time delay for currently displayed value in seconds
ERRC
-----
Error display:
0:
-ok-
no error
1:
max
exceeding pos. meas. range
2:
min
exceeding neg. meas. range
3:
dig1
switching output 1 error
4:
dig2
switching output 2 error
5:
anao
analog output error
6:
sens
sensor error
7:
data
data error (EEProm)
8:
prog
program error
9:
cal
calibration error
11