Ekinex EK-HC1-TP Manual
Navegue en línea o descargue pdf Manual para Controlador Ekinex EK-HC1-TP. Ekinex EK-HC1-TP 5 páginas. Controllers for fan coil
Actuators / controllers for fan_coil
Code
: EK-HA1-TP / EK-HB1-TP / EK-HC1-TP
KNX devices with function of actuator and tempera-
ture controller for convectors and
in KNX installations for control of homes and build-
ings.
Descrizione
The EK-Hx1-TP series includes three devices ekinex
KNX
S-mode
suitable
applications. The EK-HC1-TP is used for installations in
2 or 4-pipe hydraulic distribution systems with ON / OFF
control of an electrothermal actuator on a shut-off valve;
control of a 3-speed fan or 0-10 V control of a fan with
brushless motor; this version allows manual control of
the outputs through the membrane pushbuttons. The
EK-HA1-TP version is used for installations in 2-pipe
hydraulic distribution systems with ON / OFF control of
an electrothermal actuator on a shut-off valve and a 3-
speed fan. EK-HB1-TP version is used for installations
in 2-pipe hydraulic distribution systems with ON / OFF
control of an electrothermal actuator on a shut-off valve
and 0-10 V control of a fan with brushless motor.
The devices can be configured as actuators for the
control of a fan and a maximum of two shut-off valves
ON / OFF on the heat exchange coils , in combination
with a room thermostat installed on the KNX network .
The devices can be configured as controllers / actuators
with acquisition of the temperature of a room sensor
KNX or via a sensor installed on the return duct and
connected to one of the analog inputs.
Data sheet STEKHC1TP_EN
fan-coil. To be used
for
temperature
control
Functions
EK-HA1-TP
•
Power supply from the bus and auxiliary power
supply
•
230 Vac 50/60 Hz
Control of 2-pipe hydraulic distribution systems with
•
shutoff valve ON/OFF (1 SPST relay)
3 relay outputs to control a 3-speed fan
2 inputs freely configurable for acquisition of passive
•
temperature sensors (10 kΩ NTC at 25°C) or as
•
potential-free binary inputs
EK-HB1-TP
•
Power supply from the bus and auxiliary power
supply 230 Vac 50/60 Hz
•
Control of 2-pipe hydraulic distribution systems with
shutoff valve ON/OFF (1 SPST relay)
•
1 output 0-10 V for control of a fan with brushless
motor
•
2 inputs freely configurable for acquisition of passive
temperature sensors (10 kΩ NTC at 25°C) or as
potential-free binary inputs
EK-HC1-TP
•
Power supply from the bus and auxiliary power
supply 230 Vac 50/60 Hz
•
Control of 2 or 4-pipe hydraulic distribution systems
•
With shutoff valve ON/OFF (2 SPST relays)
•
Control of a 3-speed fan or 0-10 V control of a fan
with brushless motor
•
3 inputs freely configurable for acquisition of passive
temperature sensors (10 kΩ NTC at 25°C) or as
potential-free binary inputs
Integrated Temperature Controller
•
Settings via bus with Setpoint Setpoint single or
related activated through the way HVAC System
•
ON / OFF or PWM ( pulse width modulation ) of the
water flow to the heat exchange coils
•
ON / OFF at 1-3 windows with hysteresis or PI
( Proportional Integral ) of the air flow of the fan
•
Switching heating / cooling from the bus or
automatically according to the ambient temperature
®
or according to the temperature of the fluid at
discharge
•
Ability to enable a compensation curve climatic
cooling
•
Automatic hot-start and cold -start the fan based on
the actual temperature of the heat exchanger
•
Trigger fan in case of stratification in large
environments
•
Function monitoring condensate level
•
Monitoring function operating hours with signaling
replacement filter
Technical Data
•
Bus voltage KNX :29 Vdc
•
Operating voltage : 230 Vac 50/60 Hz
•
3 Out for Fan relay (interlocked) with monostable
relays (5A/230Vac), contacts with voltage and
external power supply terminal (EK-HA1-TP and
EK-HC1-TP version)
•
1 Out 0...10V for high impedance inputs (EK-HB1-
TP and EK-HC1-TP version)
•
1 Out with monostable relay (5A/230Vac) SPST type
single pole single throw, to control the valve of
the ,thermal battery. Contact without voltage.(EK-
HA1-TP ed EK-HB1-TP version)
Page 1