DAB MCE-150/C Instrucciones de instalación y mantenimiento - Página 8

Navegue en línea o descargue pdf Instrucciones de instalación y mantenimiento para Bomba de agua DAB MCE-150/C. DAB MCE-150/C 18 páginas.

DAB MCE-150/C Instrucciones de instalación y mantenimiento
I1
Start/Stop: If input 1 is activated from the control panel (see par. 9) it will be possible to
command the switching on and off of the pump in remote mode.
I2
Economy: If input 2 is activated from the control panel (see par. 9) it will be possible to
active the set-point reduction function in remote mode.
I3
Quick Start: If input 3 is activated from the control panel, the pump is started at
the quick start frequency Fq (see advanced menu).
I4
Not enabled
With reference to the example in Figure 4, and if the EXT and Economy functions have been activated from the control panel, the
system behaviour will be as follows:
R1
R2
Open
Open
Open
Closed
Closed
Open
Closed
Closed
Figure 4: Example of Connection of Digital Inputs Start/Stop and Economy
Functions associated with the digital inputs
Figure 5: Example of Connection of Quick Start Digital Input
Pump stopped
Pump stopped
Pump running with set-point set by the user
Pump running with reduced set-point
ENGLISH
System Status
38