DAB PUMPS ACTIVE DRIVER M/M 1.1 Instrucciones de instalación y mantenimiento - Página 7
Navegue en línea o descargue pdf Instrucciones de instalación y mantenimiento para Sistemas de control DAB PUMPS ACTIVE DRIVER M/M 1.1. DAB PUMPS ACTIVE DRIVER M/M 1.1 16 páginas.
Ref.
0V connection terminal (GND) for joining I
J22 - 6
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Connection terminal: 0V DC (GND).
J22 - 7
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Remote alarm connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J14 – o1
250 Vac – 6 A max resistive load – 3 A max inductive load
Pump operating connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J14 – o2
250 Vac – 6 A max resistive load – 3 A max inductive load
Connection terminals for interconnection and exchange.
ATTENTION: For interconnection cables with a length of more than 1 m, it is
recommended to use screened cable with the braiding connected to earth (central pin
J9
number 2) on both appliances.
ATTENTION: Scrupulously respect the connection sequence between the two
appliances! (excluding A.D. M/M 1.1)
Fig. 1
IN 3
IN 2
IN 1
J 22
Primary
Active Driver
8.2
OPERATION : KEYBOARD SETTINGS
MODE
The MODE key allows you to move on to the next items in the individual menus.
SET
The SET key allows you to quit the current menu and return to normal operating status.
Press to increase the currently modifiable parameter.
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after
+
which the identifying symbol appears.
Press to decrease the currently modifiable parameter.
-
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after
which the identifying symbol appears.
When the + key or the – key is pressed, the selected value is modified and saved immediately.
Even the accidental shut-down of the machine during this phase does not cause the loss of the
newly set parameter. The SET key is used only to return to the display of the machine status. It is
not fundamental to press the SET key in order to save the changes made.
+12V
1
2
3
ACTIVE DRIVER M/T 2.2
4
5
6
7
GND
3
2
1
J 9
ENGLISH
FUNCTION
to GND.
1
o2
o1
Fig. 3
3
2
1
J 9
28
Fig. 2
J 14
Secondary
Active Driver