bolid S2000-SP4/220 Manual de instrucciones - Página 2
Navegue en línea o descargue pdf Manual de instrucciones para Unidad de control bolid S2000-SP4/220. bolid S2000-SP4/220 7 páginas. Addressable executive module
1.2
Standard Delivery
S2000-SP4/220 Addressable Executive Module
Instruction Manual
Woodscrews
Wall Plugs 6×30
Flat Head Tapping Screw 2.2х6.5
MF 1/4W-8k2-5% Resistor
Fuse 3.15 A (the spare part)
Fuse 0.25 А (the spare part)
Package
2.1
Outputs
2.1.1
The module provides control of their outputs in accordance with a given executive
program under receiving commands sent via the polling loop from the connected S2000-KDL
controller. The module also provides monitoring the connected executive circuits for open / short
circuit failures.
2.1.2
The module executes commands to switch the outputs on and off for a programmed
time.
Note: In state of an open or short circuit failure at the moment of receiving a command to switch
on, an output will not be switched on.
2.1.3
States of an output are defined by the voltage on the terminals of the output relative to
the 'N' terminal of the power input:
Circuit
Output State
Condition
Norm
Open Failure
Short Failure
Note: If an output is switched off, a short circuit failure is defined by a voltage between the
output's terminals which must not exceed 60 mV.
2.1.4
If executive devices with the effective resistance of 250 Ohm to 50 kOhm are to be
connected to the module, they should be connected directly without any additional units (see
Figure 1).
2.1.5
If the effective resistance of an executive device is less than 250 Ohm (the voltage
between output terminals is less than 0.06 V while the control current is 0.5 mA), the device must
be connected in series with two back-to-back diodes with relevant wattage and backward voltage
400 V and more (for example, a 1N4007 diode if the operational current does not exceed 1А or a
2
Item
2 OPERATION
L [R] Terminal
On
Input Voltage Value
Off
0.35 V to 4.5 V
On
Input Voltage Value
Off
On
Input Voltage Value
Off
0.3 V to 0.6 V
4.5 V to 5 V
Table 2. Standard Delivery
Q-ty
1
1
3
3
1
6
1
1
1
Table 3. States of an Output
N [R] Terminal
0.3 V to 0.9 V
0.3 V to 0.6 V
0 V to 0.3 V
0 V to 0.3 V
Input Voltage Value
0.3 V to 0.6 V