1.2.3 The current consumed by the module (without regard to connected executive
devices):
300 mA max at 12 V (all relays are switched on);
20 mA max at 12 V (all relays are switched off);
150 mA max at 24 V (all relays are switched on);
15 mA max at 24 V (all relays are switched off).
1.2.4 The number of executive relays with switching contacts is four.
1.2.4.1 The maximum switching current of each relay (continuous load) is:
− 7(10
− 7(10*) A for a resistive load at 30 V dc;
− 4 A for an inductive load (cosϕ = 0.4) at 250 V ac;
− 4 A for an inductive load at 30 V dc.
1.2.4.2 The maximum switching power of each relay is:
− 300 W max for dc;
− 2500 VA max for ac.
1.2.4.3 The maximum switching voltage of each relay is:
− 280 V at 8 A ac;
− 125 V at 0.5 A dc.
1.2.4.4 The minimum switching load for each output is 6 V at 0.1 A
1.2.5 The overall dimensions of the module are 157 mm x 107 mm x 36 mm.
1.2.6 The weight of the module doesn't exceed 0.35 kg.
1.2.7
The pre-operation time of the module since its powering on is 5 s max.
1.3 Standard Delivery
1) S2000-SP1 mod.01 Executive Relay Module
2) Instruction Manual
3) Installation Manual
4) Woodscrews
5) Wall Plugs
6) DIN 7982 Flat Head Tapping Screw 2.2х6,5
7) Fuse 10 A
8) Package
1.4 Performance
1.4.1 Operating algorithms of the module's relays are defined in the configuration of the
network controller (either S2000 console or PC under ORION Pro software), which controls
the relays by means of commands being sent to the S2000-SP1 mod.01 relay module over
the RS-485 interface bus.
1.4.2 The module provides executing the following commands received over the RS-485
interface:
Reading the configuration parameters stored in the module's non-volatile memory;
Writing the configuration parameters stored in the module's non-volatile memory;
Assigning a network address to the module;
10 A for a short time load (no more than for a minute with the pauses between switching on of min 20
minutes)
2
) A for a resistive load (cosϕ = 1) at 250 V ac;
– 1 pc.
– 1 pc.
– 1 pc.
– 3 pcs.
– 3 pcs.
– 1 pc.
– 2 pcs.
– 1 pc.