Akytec ITP14-G Manual del usuario - Página 10

Navegue en línea o descargue pdf Manual del usuario para Instrumentos de medida Akytec ITP14-G. Akytec ITP14-G 10 páginas. Universal process indicator

2. When setting the signal limits, take into account that in some cases the correct value
cannot be displayed though there is no error indication.
Example 1:
di.Lo: -999 -> 4 mA
For the input current of 3.8 mA the correct indication should be "-1068". Actually "1068" will
be displayed.
Example 2:
di.Lo: -999 -> 4 mA
For the input current of 20.8 mA the correct indication should be "10548". Actually "0548" will
be displayed.

8 Maintenance

The maintenance includes:
cleaning the housing and the terminals from dust, dirt and debris
checking the fastening of the device
checking the wiring (connecting leads, fastenings, mechanical damage)
The device should be cleaned with a damp cloth only. No abrasives or solvent-containing
cleaners may be used.

9 Transportation and storage

Pack the device in such a way as to protect it reliably against impact for storage and
transportation. The original packaging provides optimum protection.
If the device is not taken immediately after delivery into operation, it must be carefully stored
at a protected location. The device should not be stored in an atmosphere with chemically
active substances.
Permitted storage temperature: -25...+55 °C
The device may have been damaged during transportation.
NOTICE
Check the device for transport damage and completeness!
Report the transport damage immediately to the shipper and akYtec GmbH!

10 Scope of delivery

ITP14
Gasket
Mounting nut
User guide

Appendix A. Dimensions

To prevent the device spinning, the borehole in the front panel must correspond to the
dimensions in Fig. A.2.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
di.Hi: 9999 -> 20 mA
di.Hi: 9999 -> 20 mA
Fig. A1
1
1
1
1
Fig. A2
www.akytec.de
9