Akytec ITP15 Manual del usuario - Página 6

Navegue en línea o descargue pdf Manual del usuario para Instrumentos de medida Akytec ITP15. Akytec ITP15 10 páginas. Led bargraph indicator

Akytec ITP15 Manual del usuario

6 Configuration

Each of the 10 display segments can be in one of the following states:
off
green light
red light
fast flashing (red/green)
slow flashing (red/green)
The display is shown in drawn in horizontal position. The following symbols are used:
The display segments light green or red depending on the input signal value and the set
alarm limits (sect. 6.1.). The NPN output can be switched on/off using the same alarm limits
(Table 6.2, parameter 2).
The indicator can be configured with 3 function buttons on the rear part of the device (Table
6.1).
Table 6.1 Function buttons
Press the
shown on the display as follows:
The number of red segments on the right side of the display is the parameter number.
Press the button
The number of green segments on the left side of the display is the parameter value
x10%. Use the buttons
segment is the one being currently changed.
All parameters and its values are explained in Table 6.2. Default values are highlighted in
bold.
Table 6.2 Configuration parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·
Fig. 6.1 Diagram symbols
Button
Press > 3 s:
Press < 1 s:
Increase value
Press > 3 s:
Press < 1 s:
button for 3 seconds to enter the configuration mode. The first parameter will be
to save the parameter and go to the next one.
and
to change the parameter value. The slow flashing
No.
Name
Value
4-20 mA
Signal
1
type
0-20 mA
Description
start alarm limits adjustment
save the parameter and go to the
next one
start configuration
decrease value
Display
www.akytec.de
5